Samson TROVIS 5578-E Translation Of Original Instructions Download Page 28

28  

KA 5578-E EN

Operation

5.6 

Operating the controller in manual mode

Switch to manual mode to configure all controller outputs.

System damage caused by frost when manual operating mode is active!

The frost protection function is deactivated in the manual operating mode.

 

Î

Do not run the heating during cold weather in the manual mode for long periods of time.

Manually changing the positioning value/switching state:

Turn the rotary switch to   (manual mode). The outputs of 

the configured system are listed on the display.

 

q

Select the output 

 Positioning value 

 Circulation pump (heating) 

 Storage tank charging pump 

 Circulation pump (DHW) 
 Solar circuit pump

 

q

Activate editing mode for the output.

 

q

Change the positioning value/switching state.

 

q

Confirm the positioning value/switching state.

 

The modified values remain active as long as the control

-

ler is in manual mode.

Turn the rotary switch to   (operating level). The manual 
mode is deactivated.

The outputs of the controller are not affected by merely turning the rotary switch to   (manu-
al mode). The outputs are only changed by entering or changing the positioning values or 
switching states.

NOTICE

!

Note

Summary of Contents for TROVIS 5578-E

Page 1: ...Translation of original instructions KA 5578 E EN Edition May 2022 QUICK GUIDE TROVIS 5578 E Heating and District Heating Controller...

Page 2: ...R WARNING NOTICE Note Tip 2 KA 5578 E EN Notes on this document This quick guide assists you in mounting and operating the device safely The instructions in this quick guide are binding for handling S...

Page 3: ...e 10 5 2 2 Setting the times of use 12 5 2 3 Setting the party timer special time of use 15 5 2 4 Programming public holidays special times of use 16 5 2 5 Programming vacation periods special times o...

Page 4: ...or any other financial loss except the damage was caused intentionally or by gross negligence If an essential term of the contract is breached by negligence SAMSON s liability is limited to the fores...

Page 5: ...ND GND GND AA2 AA3 AA4 42 32 31 BA1 BA2 BA5 BA6 BA7 45 46 47 44 43 SLP 41 40 39 38 37 36 35 34 33 44 41 Rk1_3 Pkt Rk2_3 Pkt Rk2_2 Pkt Rk1_2 Pkt M Bus AF2 R F4 F1 A SF1 SF2 RF1 RF2 VF1 VF2 VF3 VF4 R F1...

Page 6: ...entiometer PWM Pulse width modulation RF Room sensor RK Control circuit R F Return flow sensor SF Storage tank sensor SLP Storage tank charging pump UP Circulation pump heating VF Flow sensor ZP Circu...

Page 7: ...om Panel 1 For RK2 7 18 TROVIS 5578 E 17 1 2 3 Type 5257 5 x Room Panel 1 For RK3 1 Type 5244 no longer available Fig 3 Wiring of a room panel for RK1 RK2 or RK3 Table 1 Permissible wire cross section...

Page 8: ...n Turn q Select readings parameters and function blocks Press Confirm adjusted selection or settings Rotary switch The rotary switch is used to set the operating mode and the relevant parameters for e...

Page 9: ...ost protection is activated HC DHW Automatic mode During the programmed times of use the controller works in day mode Outside these times of use the controller is in night mode unless control operatio...

Page 10: ...ting mode The controller is usually in automatic mode 5 2 Schedules The controller operates according to the schedules in automatic mode 5 2 1 Setting the time and date The current time and date need...

Page 11: ...Select Date dd mm q Activate editing mode for the date The date reading is inverted T Change date day month Confirm the date setting T Select Year Activate editing mode for the year The year reading i...

Page 12: ...ivation Turn the rotary switch back to operating level The correct time is guaranteed after a power failure of 24 hours Normally the correct time is still retained at least 48 hours after a power fail...

Page 13: ...ing circuit HC13 DHW heating Circulation pump DHW CP Only those control circuits are available for selection which can be controlled by the selected system Activate editing mode for the control circui...

Page 14: ...15 minutes Confirm the stop time The start time of the second time of use period can now be edited To set the second and third times of use periods repeat steps with gray background If no further tim...

Page 15: ...h 0 to 48 h in steps of 15 minutes Turn the rotary switch to special times of use The party timer for the first control circuit is now selected T Set time for party mode of another control circuit if...

Page 16: ...trol circuit is now selected T Select Public holidays Start the public holiday setting The first public holiday setting is now selected is displayed if no public hol idays default setting have been pr...

Page 17: ...e The system runs constantly in reduced mode during vacation periods A maximum of ten va cation periods can be entered Each vacation period can be separately assigned to the heat ing circuits HC1 HC2...

Page 18: ...the year setting All is selected The vacation period then applies to all control circuits T If the vacation period is to be only valid for one control circuit select the required control circuit Heati...

Page 19: ...rm vacation period T Select Confirm setting The vacation period is deleted After programming all vacation periods T Select Back Exit the vacations setting Turn the rotary switch back to operating leve...

Page 20: ...to 40 0 C HC12 room temperature 20 0 C 0 0 to 40 0 C HC13 room temperature 20 0 C 0 0 to 40 0 C DHW temperature 60 0 C Min to max DHW temperature HC1 OT deactivation value 22 0 C 0 0 to 50 0 C HC2 OT...

Page 21: ...e available for se lection which can be controlled by the selected system The deactivation values are located in a separate menu de activation values for systems with three control circuits T Select t...

Page 22: ...the controller display during operation The con troller display usually shows the date time and an actual temperature when the rotary switch is switched to the Operating level position Outdoor tempera...

Page 23: ...heating ON OFF The following applies for DHW heating Current operating mode Pump ON OFF Storage tank charging pump Circulation pump DHW Solar circuit pump See section 5 1 for further information T Sel...

Page 24: ...of the system section shown are displayed T Special values Measured values from additional sensor inputs not relevant to closed loop control or from the 0 to 10 V inputs are displayed T Alarm list The...

Page 25: ...in the extended operating level Turn the rotary switch to settings T Enter code number 1999 Confirm key number Turn the rotary switch to operating level T Select Information The additional meter page...

Page 26: ...he Start up section 5 5 1 Adapting the Trend Viewer The standard graph shows the data measured at the outdoor sensor AF1 and flow sensor VF1 plotted over time Open the Trend Viewer Adding measuring da...

Page 27: ...ne T Select Scroll Activate editing mode for scroll function T Shift the time line Confirm time display Zooming in out T Select Zoom Open zoom function T Zoom in or out Confirm display Closing the Tre...

Page 28: ...configured system are listed on the display T Select the output Positioning value Circulation pump heating Storage tank charging pump Circulation pump DHW Solar circuit pump T Activate editing mode f...

Page 29: ...78 E Max charging temp Max charging temperature reached See DHW heating in the storage tank charging system function in Annex A configuration instructions of the Mounting and Operat ing Instructions u...

Page 30: ......

Page 31: ......

Page 32: ...023 08 11 English 4000237084 SAMSON AKTIENGESELLSCHAFT Weism llerstra e 3 60314 Frankfurt am Main Germany Phone 49 69 4009 0 Fax 49 69 4009 1507 samson samsongroup com www samsongroup com KA 5578 E EN...

Reviews: