Functions of the heating circuit
Which controller functions are available depends on the selected system code number (Anl).
5.1
Weather-compensated control
When weather-compensated control is used, the flow temperature is controlled according to
the outdoor temperature. The heating characteristic in the controller defines the flow temper-
ature set point as a function of the outdoor temperature (–> Fig. 5). The outdoor temperature
required for weather-compensated control can either be measured at an outdoor sensor or
received from a connected device bus.
Functions
WE
Configuration
Outdoor sensors AF1/2
1
CO1, 2 -> F02 - 1
If you wish to alternatively receive the outdoor temperature via the device bus, the following
additional configurations must be made:
Device bus
0
CO7 -> F01 - 1; device bus address
Receive value AF1
0
CO7 -> F07 - 1; register no.
Receive value AF2
0
CO7 -> F09 - 1; register no.