Parameters
WE
Parameter level / Range of values
Outdoor temperature
Point 1
Point 2
Point 3
Point 4
–10 °C
– 5 °C
5 °C
10 °C
PA2*, PA3*, PA5 / –20 to 50 °C
Flow temperature
Point 1
Point 2
Point 3
Point 4
90 °C
80 °C
68 °C
50 °C
PA2*, PA3*, PA5 / 20 to 160 °C
Set-back difference
Points
½
Points
3/4
15 °C
20 °C
PA2*, PA3*, PA5 / 0 to 30 °C
Max. flow temperature
90 °C
PA2*, PA3* / 20 to 160 °C
Min. flow temperature
20 °C
PA2*, PA3* / 20 to 120 °C
* Only in systems Anl 1 to 3 with Co5 -> Fb13 = ON
8.2
Fixed set point control
During the times-of-use, the flow temperature can be controlled according to a fixed
Set point.
Outside the times-of-use, this
Set point is reduced by the Set-back difference.
The fixed set point control is activated when there is no outdoor sensor AF connected to the sys-
tem or when it has been configured in the function block
Type of characteristic
. In the case that
the fixed set point control is configured and an outdoor sensor is connected, the outdoor tem-
perature is displayed in the InF5 level. The outdoor temperature does not have any effect on the
control loop.
Functions
WE
Configuration
Type of characteristic
OFF
Co5 -> Fb03 = OFF
Type of characteristic for separate/
direct heating circuit*
OFF
Co2, Co3 -> Fb10 = OFF*
* Only in systems Anl 1 to 3 with Co5 -> Fb13 = ON
Parameters
WE
Parameter level / Range of values
Flow temperature set point
70 °C
PA2*, PA3*, PA5 / 20 to 160 °C
Set-back difference
15 °C
PA2*, PA3*, PA5 / 0 to 30 °C
* Only in systems Anl 1 to 3 with Co5 -> Fb13 = ON
52
EB 5474 EN
System-wide functions