Troubleshooting
Errors on the LCD by the word
ERROR
written
at the top and the associated error code
(e.g.
16
) being shown at the bottom of the
display.
Refer to table 6 for descriptions of the error
codes.
Press
key to reset or confirm errors.
Depending on the error class, Media 6 re-
sponds differently when the
key is pressed:
Class E1
: Device is restarted.
Class E2
: Error is suppressed for 8 s.
Class E3
: Error is reset.
Class E4
: Error is reset.
All errors in Classes E1 to E3 are logged in an
error history and can be read or viewed in
TROVIS-VIEW (version V3.11 and higher).
Errors are not saved; only the current error
switches the device to error mode.
For errors in Classes E1 and E2, the signal
current is set to
≤
3.6 mA.
EB 9527-3 EN
29
Troubleshooting
Table 6
· Error codes
Error code
Description
Class
1
Oscillating circuit of differential inductor failed
E1
2
Checksum error RAM
E1
4
Checksum error FRAM
E1
8
Span outside permissible range
E2
16
Error in tank characteristic
E2
32
Δ
p sensor calibration
E2
128
Invalid memory pen
E4
256
Checksum error memory pen
E4
512
Communication error memory pen
E4
4096
Internal communication error
E1
8192
No default calibration available
E1
16384
No LCD available
E3
32768
Crystal oscillator failed
E3
Note!
Error codes can also be added up and displayed as a sum of codes, e.g. FC
8
and FC
16
-> ERROR
24