Note!
When using reverse installation, i.e. with the
meter mounted above the measuring point,
the differential pressure lines may partly get
drained when depressurizing the system.
When starting up the system again, vent the
arranged measuring system, allowing it to fill
with condensate.
When measuring liquids
1.
Open
high-pressure line by slow turn-
ing.
2.
Close
equalizing valve or bypass of the
valve block.
3.
Open
low-pressure line.
4. Loosen vent screw on the dp cell and
retighten it when the air has escaped.
5. Check zero (see section 6.3) and put the
device back into operation.
5.3 Draining
When measuring gas, drain condensed wa-
ter from the equalizing tanks from time to
time.
Warning!
Close valves in the differential pressure lines
(valve block) before opening the drain plugs.
EB 9527-3 EN
21
Start-up