8
IP 9519-1 EN
Installation
A measuring span calibration is possible in
the pointer range
>95°
(based on the point
-
er's zero point, see Fig. 12).
The
red
LED is permanently lit (error indica-
tion) if the calibration range is exceeded.
Activate
span calibration
level
Key
LED
Function
2x
key
Green
Blinking pattern
key
Red
Span calibration active
The
red
LED blinks briefly
once to indicate that calibra
-
tion is in progress. Current
pointer position
=
20 mA.
Green
Change to standard opera
-
tion
270°
>95°
135°
0°
≈
–5°
Zero adjustment range
Span adjustment range
Fig. 12:
Zero and span calibration ranges
Characteristic
Three characteristics are available.
−
Linear
−
Root-extracting
−
User-defined
(factory set
-
ting)
Activate
characteristic
level
Key
LED
Function
3x
key
Green
Blinking pattern
key
Red
The blinking pattern indicates
which characteristic is currently
selected.
key
Red
Every time the key is pressed,
the blinking pattern changes:
Blinking pattern
=
Characteris
-
tic.
key
Red
Confirm.
Green
Change to standard operation
4 mA/20 mA ammeter
To calibrate the assessment unit, 4 and
20 mA test signals are issued.
Activate
4 mA/20 mA ammeter
level
Key
LED
Function
4x
key
Green
Blinking pattern
key
Red
Blinking pattern
=
4 mA output.
key
Red
Blinking pattern
=
20 mA output.
key
Red
Exit function.
Green
Change to standard opera
-
tion