IP 9519-1 EN

Installation

A measuring span calibration is possible in 
the pointer range 

>95°

 (based on the point

-

er's zero point, see Fig. 12).

The 

red

 LED is permanently lit (error indica-

tion) if the calibration range is exceeded.

Activate 

span calibration

 level

Key

LED

Function

2x

 key

Green

Blinking pattern 

 key

Red

Span calibration active

The 

red

 LED blinks briefly 

once to indicate that calibra

-

tion is in progress. Current 

pointer position 

=

 20 mA.

Green

Change to standard opera

-

tion

270°

>95°

135°

 

–5°

Zero adjustment range

Span adjustment range

Fig. 12: 

Zero and span calibration ranges

Characteristic

Three characteristics are available.

 

Linear 

 

Root-extracting 

 

User-defined 

 (factory set

-

ting)

Activate 

characteristic

 level

Key

LED

Function

3x

 key

Green

Blinking pattern 

 key

Red

The blinking pattern indicates 

which characteristic is currently 

selected.

 key

Red

Every time the key is pressed, 

the blinking pattern changes:

Blinking pattern 

=

 Characteris

-

tic.

 key

Red

Confirm.

Green

Change to standard operation

4 mA/20 mA ammeter

To calibrate the assessment unit, 4 and 
20 mA test signals are issued.
Activate 

4 mA/20 mA ammeter

 level

Key

LED

Function

4x

 key

Green

Blinking pattern 

 key

Red

Blinking pattern 

 

=

 4 mA output.

 key

Red

Blinking pattern 

 

=

 20 mA output.

 key

Red

Exit function.

Green

Change to standard opera

-

tion

Summary of Contents for Media 5

Page 1: ...Material number 3 Serial number 4 QR code to go to product documentation 3 1 2 WARNING POTENTIAL ELECTROSTATIC CHARGING HAZARD SEE INSTRUCTIONS Module Made in Germany SAMSON AG Germany Firmware Mater...

Page 2: ...sions The following applies to the version with explosion protection 100049064 1 When working on explosion protected versions of the option module personnel must undergo special training or instruc ti...

Page 3: ...R 600 at 24 V and 20 mA Power consumption 0 252 mW for 12 V DC and 21 mA Settings Zero calibration Span calibration Characteristic selection Test function Characteristic Output and reading linear or...

Page 4: ...eas Dial screws Housing screws Cover plate Fig 3 Standard version of Media 5 Indicat ing unit with cover plate 1 Undo the four housing screws Remove the housing cover 2 Unscrew the two dial plate scre...

Page 5: ...r weight Mating plate Pointer axis Pointer Fig 5 Fixing the magnetoresistive measuring system 6 If the terminal board has not yet been connected connect the connecting cable and connector at the back...

Page 6: ...nsists of an actively controlled current loop with a 4 to 20 mA loop current This current depends on the position of the pointer on the Media 5 device Pointer position 0 to 270 corresponds with the 4...

Page 7: ...n Characteristic 4 mA 20 mA ammeter Zero calibration The electric zero is adapted to the mechani cal zero As a result a 4 mA signal is also issued at p 0 bar corresponding to the pointer s zero point...

Page 8: ...ero and span calibration ranges Characteristic Three characteristics are available Linear Root extracting User defined factory set ting Activate characteristic level Key LED Function 3x key Green Blin...

Page 9: ...according to explosion protection requirements has issued an inspection certificate or given the device a mark of conformity Inspection by a qualified inspector is not required if the manufacturer per...

Page 10: ...2020 09 11 English SAMSON AKTIENGESELLSCHAFT Weism llerstra e 3 60314 Frankfurt am Main Germany Phone 49 69 4009 0 Fax 49 69 4009 1507 samson samsongroup com www samsongroup com IP 9519 1 EN...

Reviews: