Installation

3  Installation

Risk of fatal injury due to the ignition of an 

explosive atmosphere.

 

Î

For mounting and electrical installation in 
hazardous areas, observe the explosion 
protection approvals as well as the 
relevant electrotechnical regulations and 
the accident prevention regulations that 

apply in the country of use. EN 60079-

14 applies in Europe.

 

Î

Installation, operation or maintenance of 

the differential pressure and flow meter 

must only performed by personnel with 

qualifications according to Clause 4.5 of 
IEC 60079-14 who has undergone 

special training or instructions or who is 

authorized to work on explosion-

protected devices in hazardous areas.

Dial screws

Housing screws

Cover plate

Fig. 3: 

Standard version of Media 5 · Indicat-

ing unit with cover plate

1.  Undo the four housing screws. Remove 

the housing cover.

2.  Unscrew the two dial plate screws and 

remove the cover plate. Retighten dial 
plate screws.

3.  Place the magnetoresistive measuring 

system on the pointer.

 

Self-adhesive dot on film: pull off 
brown backing.

 

Stick the film with self-adhesive dot, 
adhesive side facing downward, cen-
trally on the pointer axis.

 

Pull off film. Make sure that the 
self-adhesive dot remains stuck on.

 

Place the magnetoresistive measuring 
system, with the 

arrow

 pointing to

-

ward the 

pointer

, onto the pointer 

axis. Press it down.

Pointer axis before 

attachment

Pointer axis with self-

adhesive dot · Film pulled 

off

Fig. 4: 

Attaching the magnetoresistive measur

-

ing system

4. 

Turn the pointer from the zero position to 

the approx. 90° position.

DANGER

!

Summary of Contents for Media 5

Page 1: ...Material number 3 Serial number 4 QR code to go to product documentation 3 1 2 WARNING POTENTIAL ELECTROSTATIC CHARGING HAZARD SEE INSTRUCTIONS Module Made in Germany SAMSON AG Germany Firmware Mater...

Page 2: ...sions The following applies to the version with explosion protection 100049064 1 When working on explosion protected versions of the option module personnel must undergo special training or instruc ti...

Page 3: ...R 600 at 24 V and 20 mA Power consumption 0 252 mW for 12 V DC and 21 mA Settings Zero calibration Span calibration Characteristic selection Test function Characteristic Output and reading linear or...

Page 4: ...eas Dial screws Housing screws Cover plate Fig 3 Standard version of Media 5 Indicat ing unit with cover plate 1 Undo the four housing screws Remove the housing cover 2 Unscrew the two dial plate scre...

Page 5: ...r weight Mating plate Pointer axis Pointer Fig 5 Fixing the magnetoresistive measuring system 6 If the terminal board has not yet been connected connect the connecting cable and connector at the back...

Page 6: ...nsists of an actively controlled current loop with a 4 to 20 mA loop current This current depends on the position of the pointer on the Media 5 device Pointer position 0 to 270 corresponds with the 4...

Page 7: ...n Characteristic 4 mA 20 mA ammeter Zero calibration The electric zero is adapted to the mechani cal zero As a result a 4 mA signal is also issued at p 0 bar corresponding to the pointer s zero point...

Page 8: ...ero and span calibration ranges Characteristic Three characteristics are available Linear Root extracting User defined factory set ting Activate characteristic level Key LED Function 3x key Green Blin...

Page 9: ...according to explosion protection requirements has issued an inspection certificate or given the device a mark of conformity Inspection by a qualified inspector is not required if the manufacturer per...

Page 10: ...2020 09 11 English SAMSON AKTIENGESELLSCHAFT Weism llerstra e 3 60314 Frankfurt am Main Germany Phone 49 69 4009 0 Fax 49 69 4009 1507 samson samsongroup com www samsongroup com IP 9519 1 EN...

Reviews: