EB 8061 EN
5-5
Installation
5.3.1 Mounting the external
anti-rotation fixture
Before mounting the actuator, the external
anti-rotation fixture must be mounted onto
the plug stem in some cases. The valve must
be closed beforehand.
For SAMSON Type 3271 and Type 3277
Actuators with Type 3273 Hand-operated
Actuator, observe the mounting and operat-
ing instructions of the hand-operated actua-
tor (handwheel) to mount the anti-rotation
fixture
u
a) Standard version for
Series 250 Valves, NPS 6
and larger
See Fig. 5-1 and Fig. 5-2
1. Insert ball bearings (310) into the recess-
es in the bonnet.
2. Place the yoke (3) on the bonnet in such
a way that the ball bearings fit into the
recesses of the yoke.
3. Fasten the yoke (3) using the castellated
nut (92).
4. Fasten the hanger (83) and warning la-
bel (255), if applicable, to the yoke us-
ing the screws (82).
5. Position the travel indicator scale (84) on
the hanger (83) with the screws (85) ac-
cording to Table 5-4.
6. Use a soft-faced hammer or lever press
to press the sliding washers (309) with
their beveled part first (without using any
lubricant) into the recesses of the clamps
3
83
82
82
310
310
92
84
85
255
Legend
3
Yoke
82
Screws
83
Hanger
84
Travel indicator scale
85
Screws
92
Castellated nut
255 Warning label
310 Ball bearing
Plug stem
Fig. 5-1:
Overview of yoke assembly with travel indicator scale in the standard version
on each side (see detailed view Y in
Fig. 5-2).
− The anti-rotation fixture does not get
stuck on the yoke and can move free-
ly in the direction of travel.
14. Extend the actuator stem again and
mount the stem connector clamps.
Summary of Contents for EB 8061 EN