![Samson 5343 Mounting And Operating Instructions Download Page 16](http://html1.mh-extra.com/html/samson/5343/5343_mounting-and-operating-instructions_3826406016.webp)
3-4
EB 5206 EN
Design and principle of operation
Materials
Bottom section of the housing
PA (reinforced)
Housing cover
ABS with window (PMMA)
Temperature sensor, capillary
tube
Cu (copper)
Weight
Single thermostat approx. 0.225 kg
Double thermostat approx. 0.45 kg
Conformity
1)
Testing according to
DIN EN 14597 (Types 5343, 5344
and 5345)
1)
No EAC compliance for Type 5349
Table 3-2:
Technical data (depending on type)
Type
Set point range
Switching
differential
Switching point accuracy
Maximum
medium
temperature
Safety temperature monitors (STM)
5343-1
0 to 60 °C
8 K
Range: 0 to 25 °C
0 K –8.5 K
85 °C
Range: 25 to 35 °C
0 K –6.0 K
Range: 35 to 60 °C
0 K –8.5 K
5343-2
40 to 100 °C
8 K
Range: 40 to 100 °C
0 K –8.5 K
125 °C
5343-3
70 to 130 °C
8 K
Range: 70 to 130 °C
0 K –8.5 K
155 °C
5343-4
35 to 95 °C
8 K
Range: 35 to 95 °C
0 K –8.5 K
120 °C
Temperature regulators (TR)
5344-1
0 to 120 °C
3 K
Range: 0 to 80 °C
+7.2 K –7.2 K
145 °C
Range: 80 to 120 °C
+3.6 K –3.6 K
5344-2
20 to 150 °C
4 K
Range: 20 to 106 °C
+7.8 K –7.8 K
175 °C
Range: 106 to 150 °C
+3.9 K –3.9 K
Summary of Contents for 5343
Page 12: ...2 2 EB 5206 EN...
Page 22: ...3 10 EB 5206 EN...
Page 32: ...5 8 EB 5206 EN...
Page 34: ...6 2 EB 5206 EN...
Page 36: ...7 2 EB 5206 EN...
Page 38: ...8 2 EB 5206 EN...
Page 42: ...10 2 EB 5206 EN...
Page 44: ...11 2 EB 5206 EN...
Page 48: ...13 2 EB 5206 EN...
Page 50: ...14 2 EB 5206 EN...
Page 55: ...EB 5206 EN 15 5 Certificates TR CU certificate...
Page 56: ...15 6 EB 5206 EN Certificates...
Page 59: ......