6.6 Ammeter function
In order to check the functioning of con-
nected devices, an output signal of 4 to 20
or 22.8 mA can be adjusted for a short
time regardless of the current liquid level in
the tank.
Media 6 with LCD
Write protection: turn switch
4
OFF
.
4 mA ammeter
Press and
hold down
key.
Press within 8 seconds and hold down,
output signal I = 4.0 mA.
Release to change the signal between
4.0 mA and 22.8 mA.
Release
key, current signal I indicates
the mA value corresponding to the tank
capacity.
20 mA ammeter
Press and
hold down
key.
Press within 8 seconds and hold down,
output signal I = 20.0 mA.
Release to change the signal between
20.0 mA and 22.8 mA.
Release key, current signal I indicates the
mA value corresponding to the tank
capacity.
Write protection: turn switch
4
ON
.
Media 6 with LED
Write protection: turn switch
4
OFF
.
4 mA ammeter
Press and
hold down
key.
Press within 8 seconds and hold down,
output signal I = 4.0 mA, signaled by
rapid flashing of the LED.
Press to change the signal between
4.0 mA and 22.8 mA (LED on).
Release
key, current signal I indicates
the mA value corresponding to the
tank capacity (LED off).
20 mA ammeter
Press and
hold down
key.
Press within 8 seconds and hold down,
output signal I = 20.0 mA, signaled by
slow flashing of the LED.
Press to change the signal between
20.0 mA and 22.8 mA (LED on).
Release
key, current signal I indicates the
mA value corresponding to the tank
capacity. The LED goes out.
Write protection: turn switch
4
ON
.
EB 9527-1 EN
23
Setting
Summary of Contents for 5006-0
Page 5: ...Previous version New version EB 9527 1 EN 5...
Page 30: ...30 EB 9527 1 EN...
Page 31: ...EB 9527 1 EN 31...
Page 32: ...32 EB 9527 1 EN...
Page 33: ...EB 9527 1 EN 33...