24
EB 8365 EN
Servicing explosion-protected devices
6
Servicing explosion-protected
devices
If a part of the device on which the explosion
protection is based needs to be serviced, the
device must not be put back into operation
until a qualified inspector has assessed it ac
-
cording to explosion protection require-
ments, has issued an inspection certificate or
given the device a mark of conformity.
Inspection by a qualified inspector is not re
-
quired if the manufacturer performs a rou-
tine test on the device prior to putting it back
into operation. Document the passing of the
routine test by attaching a mark of conformi-
ty to the device.
Replace explosion-protected components on-
ly by original, routine-tested components
provided by the manufacturer.
Devices that have already been used outside
hazardous areas and are intended for future
use inside hazardous areas must comply
with the safety requirements placed on ser-
viced devices. Before being operated inside
hazardous areas, test the devices according
to the specifications for servicing explosion-
protected devices.
7
Maintenance and calibration
Interconnection with intrinsically safe circuits
to check or calibrate the equipment inside or
outside hazardous areas is to be performed
only with intrinsically safe current/voltage
calibrators and measuring instruments to
rule out any damage to components relevant
to explosion protection.
Î
Observe the maximum permissible val-
ues specified in the certificates for intrin
-
sically safe circuits.
Summary of Contents for 4746
Page 4: ......
Page 27: ...EB 8365 EN 27...
Page 28: ...28 EB 8365 EN...
Page 29: ...EB 8365 EN 29...
Page 30: ...30 EB 8365 EN...
Page 31: ...EB 8365 EN 31...
Page 32: ...32 EB 8365 EN...
Page 33: ...EB 8365 EN 33...
Page 36: ...36 EB 8365 EN...
Page 37: ...EB 8365 EN 37...
Page 38: ...38 EB 8365 EN...
Page 39: ...EB 8365 EN 39...