![Samson 4708-5352 Mounting And Operating Instructions Download Page 12](http://html1.mh-extra.com/html/samson/4708-5352/4708-5352_mounting-and-operating-instructions_3997568012.webp)
Type 4708-58xx for Type 3761 Positioner
1. Screw the special nut (5) into the SUPPLY
connecting hole of the positioner.
2. Push the special hollow screw (6) into
the connection hole of the adapter plate
(1).
3. Insert the O-ring (9). Position the supply
pressure regulator and fasten it to the
positioner using the special screw.
4. Seal the spare connections with stoppers
(4) to prevent dirt from entering the de-
vice.
Type 4708-64xx for Type 3277 Actuator
Before attaching the supply pressure regula-
tor, check whether the tongue of the gasket
(1.2) is aligned at the connection block (1)
in such a way that the actuator symbol (1.3)
indicating “Actuator stem extends” or “Actu-
ator stem retracts” matches the fail-safe ac-
tion of the actuator.
If this is not the case, proceed as follows:
1. Unscrew the three Phillips screws (3.1),
lift off the cover plate (1.1) and turn the
gasket (1.2) by 180° and reinsert it.
2. Place the connection block with inserted
O-ring on the positioner and actuator
yoke and fasten it with hexagonal socket
screw (3).
3. Place the supply pressure regulator with
O-ring on the connection block and fas-
ten it with hexagonal socket screw (2).
12
EB 8546 EN
Mounting the supply pressure regulator
3
1
1.1
1.2
1.3
3.1
3.1
2
1
G3/8
138
238
G
Output
Output
S
Input
6
5
4
3
2
1
0
27
1
6
9
4
1
5
Fig. 7 · Attachment of supply pressure regulator
Summary of Contents for 4708-5352
Page 31: ...EB 8546 EN 31...