EB 2178 EN
19
Mounting and start-up
5.2.2
Installing the control thermostat
The Type 2430 is installed without thermowell.
To fully use the fast response behavior of the sensor (vapor pressure), the sensor must also be
installed at the best possible location.
In plate heat exchangers, this location is directly upstream of the outlet where the heated wa-
ter flows out of the heat exchanger.
Î
The notch at the end of the sensor must point upward (see Fig. 5).
A
Plate heat exchanger
Hot water outlet
Adapter with temperature
sensor
View A
Temperature sensor, notch facing
upward
max. ±5°
5 mm
Fig. 5:
Arrangement of Type 2430 Control Thermostat for Type 43-8
Note