EB 2517 EN
3-3
Design and principle of operation
3.1
Additional fittings
Î
See Fig. 3-2
Strainers
We recommend installing a SAMSON
strainer (2) upstream of the valve. It prevents
solid particles in the process medium from
damaging the regulator.
Î
Do not use the strainer to permanently
filter the process medium.
Î
Select a strainer (mesh size) suitable for
the process medium.
Any impurities carried along by the process
medium may impair the proper functioning
of the regulator. We recommend installing a
strainer (e.g. SAMSON Type 2 NI) upstream
of the excess pressure valve (
u
.
Note
Pressure gauges
Install a pressure gauge (3 and 5) both up-
stream and downstream of the regulator to
monitor the pressures prevailing in the plant.
Bypass and shut-off valves
We recommend installing a shut-off valve (1
and 6) both upstream of the strainer and
downstream of the regulator and installing a
bypass line. The bypass ensures that the
plant does not need to be shut down for ser-
vice and repair work on the regulator.
Insulation
Regulators can be insulated to reduce heat
energy transfer.
Refer to the instructions in the 'Installation'
section.
1 Shut-off valve
2 Strainer
3 Upstream pressure gauge
4
Excess pressure valve
5
Downstream pressure gauge
6 Shut-off valve
18 Compensation chamber, e.g. for
steam
1
2
4
3
5
6
18
Fig. 3-2:
Installation example
Summary of Contents for 41-73 Series
Page 14: ...1 10 EB 2517 EN...
Page 48: ...8 4 EB 2517 EN...
Page 60: ...11 2 EB 2517 EN...
Page 62: ...12 2 EB 2517 EN...
Page 64: ...13 2 EB 2517 EN...
Page 68: ...14 4 EB 2517 EN Certificates 2...
Page 69: ...EB 2517 EN 14 5 Certificates 3...
Page 70: ...14 6 EB 2517 EN...
Page 75: ......
Page 76: ......
Page 77: ......