EB 3966 EN
21
Design and principle of operation
Electric data
Type 3966
-0001
-0002
-0003
-0004
-0005
-0006
Nominal
signal
U
N
6 V DC
12 V DC
24 V DC
120 V DC
240 V AC
120 V AC
U
max
1)
36 V
60 V
60 V
240 V
340 V
240 V
f
N
–
–
–
–
50 to 60 Hz
Switch-
ing
point
ON
U
min. +80 °C
≥4.8 V
≥8.6 V
≥15.6 V
≥87 V
≥188 V
≥97 V
I
N
≥1.4 mA
≥1.4 mA
≥1.4 mA
≥1.9 mA
≥2.0 mA
≥1.9 mA
P
N
≥5.3 mW
≥10.4 mW
≥19.7 mW
≥209 mW
≥459 mW
≥225 mW
OFF
U
max. –45 °C
≤1.0 V
≤2.2 V
≤4.2 V
≤26 V
≤55 V
≤29 V
Type of protection Ex d IIC
2)
–
Type 3966
-2101
-2102
-2103
Nominal
signal
U
N
6 V DC
12 V DC
24 V DC
See EU type examination certificate PTB 08 ATEX 1024 for permissible
ambient temperature
Type of protection Ex ia IIC, Ex ia IIIC, Ex tb IIIC
2)
Type 3966
-1101
-1102
-1103
Nominal
signal
U
N
6 V DC
12 V DC
24 V DC
See EU type examination certificate PTB 12 ATEX 2021 for maximum
permissible values when connected to a certified intrinsically safe cir
-
cuit.
Type of protection Ex ia IIC, Ex ia IIIC, Ex tb IIIC
2)
Type 3966
-8101
-8102
-8103
Nominal
signal
U
N
6 V DC
12 V DC
24 V DC
See EU type examination certificate PTB 12 ATEX 2021 for maximum
permissible values when connected to a certified intrinsically safe
circuit.
1)
Duty cycle 100 %
2)
Summary of Contents for 3966
Page 1: ...Translation of original instructions EB 3966 EN Edition March 2019 Type 3966 Solenoid Valve...
Page 5: ...EB 3966 EN 5...
Page 41: ...EB 3966 EN 41...
Page 42: ...42 EB 3966 EN...
Page 43: ...EB 3966 EN 43...
Page 44: ...44 EB 3966 EN...
Page 45: ...EB 3966 EN 45...
Page 46: ...46 EB 3966 EN...
Page 47: ...EB 3966 EN 47...