![Samson 3760 Mounting And Operating Instructions Download Page 20](http://html.mh-extra.com/html/samson/3760/3760_mounting-and-operating-instructions_806346020.webp)
5.1 Retrofitting a limit switch
For installation of a limit switch in an i/p
positioner (model index .02 and higher;
model index .00 and .01 without explosion
protection) at a later date, a retrofit kit (or-
der no. 1400-8803) is required.
To retrofit the limit switch, the positioner
must be removed from the actuator.
1. Connect the plug of the proximity switch
cable to the plug connection (2) located
on the PCB.
2. Install support plate (8) on the aluminum
plate adjacent to the terminal base using
two screws.
3. Attach positioner to the actuator.
4. Fix bracket with pin (5) on the clamp at-
tached to the actuator stem and secure it
with screws. Make sure that the pin (5)
is located in the recess of the operating
lever (3).
5. Connect the switching amplifier to the
ter and – using cable glands or
connectors.
6. Refer to section 5 for adjustment.
20
EB 8385 EN
Adjusting the limit switch
1
2
3
4
7
5
6
8
Fig. 7 · Limit switch, for positioner with left attachment (for right attachment, drawing turned by 180°)
1
Terminal base with PCB
2
Connector
3
Operating lever
4
Adjustment screw
5
Pin
6
Notch mark
7
Switching point indicator
8
Support plate
Summary of Contents for 3760
Page 24: ...24 EB 8385 EN ...
Page 25: ...EB 8385 EN 25 ...
Page 26: ...26 EB 8385 EN ...
Page 27: ...EB 8385 EN 27 ...
Page 28: ...28 EB 8385 EN ...
Page 29: ...EB 8385 EN 29 ...
Page 30: ...30 EB 8385 EN ...
Page 31: ...EB 8385 EN 31 ...
Page 32: ...32 EB 8385 EN ...
Page 33: ...EB 8385 EN 33 ...
Page 34: ...34 EB 8385 EN ...
Page 35: ...EB 8385 EN 35 ...