EB 8384-4 EN
95
Code list
Hardware errors
Error codes –
Recommended action
Condensed state message active, when prompted,
Err
appears.
When fault alarms exist, they are displayed here.
62 x signal
Actuator's measured value recording failed.
The conductive plastic element is defective.
The device continues functioning in emergency mode but it must be replaced
as quickly as possible.
The emergency mode on the display is indicated by a blinking closed-loop op-
eration icon and 4 dashes instead of the position reading.
Note on the open-loop operation:
If the measuring system has failed, the po
-
sitioner is still in a reliable state. The positioner switches to emergency mode
where the position cannot be accurately controlled anymore. However, the po
-
sitioner continues operation according to its set point so that the process re-
mains in a safe state.
Status classification
[Maintenance demanded]
Recommended
action
Return positioner to SAMSON AG for repair.
64 i/p converter (y)
Current circuit of i/p converter interrupted.
Status classification Maintenance alarm (cannot be classified)
Recommended
action
Cannot be remedied. Return positioner to SAMSON AG for repair.
Summary of Contents for 3730-4
Page 17: ...EB 8384 4 EN 17 Design and principle of operation...
Page 105: ...EB 8384 4 EN 105...
Page 106: ...106 EB 8384 4 EN...
Page 107: ...EB 8384 4 EN 107...
Page 108: ...108 EB 8384 4 EN...
Page 109: ...EB 8384 4 EN 109...
Page 110: ...110 EB 8384 4 EN...
Page 111: ...EB 8384 4 EN 111...
Page 112: ...112 EB 8384 4 EN...
Page 113: ...EB 8384 4 EN 113...
Page 123: ...EB 8384 4 EN 123...
Page 124: ...124 EB 8384 4 EN...
Page 125: ...EB 8384 4 EN 125...