EB 8074 EN
8-1
Malfunctions
8
Malfunctions
Read hazard statements, warnings and caution notes in the 'Safety instructions and mea
-
sures' section.
8.1
Troubleshooting
Malfunction
Possible reasons
Recommended action
Actuator and plug stem
does not move on
demand.
Actuator is blocked.
Check attachment.
Remove the blockage.
WARNING!
A blocked actuator or plug stem (e.g.
due to seizing up after remaining in the same
position for a long time) can suddenly start to move
uncontrollably. Injury to hands or fingers is possible
if they are inserted into the actuator or valve.
Before trying to unblock the actuator or plug stem,
disconnect and lock the pneumatic air supply as
well as the control signal. Before unblocking the
actuator, release any stored energy in the actuator
(e.g. spring compression). See associated actuator
documentation.
Diaphragm in the
actuator defective
See associated actuator documentation.
Signal pressure too low
Check the signal pressure.
Check the signal pressure line for leakage.
Jolting movement of the
actuator and plug stem
Version with adjustable
packing
1)
: packing not
tightened correctly
Tighten the packing correctly (see information under
'Adjusting the packing' in the 'Installation' section >
'Testing the installed valve').
Actuator and plug stem
does not stroke through
the entire range.
Signal pressure too low
Check the signal pressure.
Check the signal pressure line for leakage.
Travel stop active
See associated actuator documentation.
Incorrect setting of
valve accessories
Check the settings of the valve accessories.
Summary of Contents for 3296
Page 14: ...1 10 EB 8074 EN...
Page 24: ...3 8 EB 8074 EN...
Page 30: ...4 6 EB 8074 EN...
Page 50: ...5 20 EB 8074 EN...
Page 58: ...8 4 EB 8074 EN...
Page 84: ...12 2 EB 8074 EN...
Page 86: ...13 2 EB 8074 EN...
Page 88: ...14 2 EB 8074 EN...
Page 89: ...EB 8074 EN 14 3...
Page 90: ...14 4 EB 8074 EN...
Page 93: ...EB 8074 EN 15 3 Annex...
Page 97: ......
Page 98: ......
Page 99: ......