EB 8065 EN
9-3
Servicing
We recommend the following inspection and testing which can be performed while the pro-
cess is running:
Inspection and testing
Action to be taken in the event of a negative result:
Check the markings, labels and name-
plates on the valve for their readability
and completeness.
Immediately renew damaged, missing or incorrect name-
plates or labels.
Clean any inscriptions that are covered with dirt and are
illegible.
Check the pipe connections and gaskets
on the valve and actuator for leakage.
Check the bolted joint (tightening torque).
Replace the gasket on the flanged joint as described in sec-
tion 9.4.1.
Version with adjustable packing
1)
: tighten the packing (see
information under 'Adjusting the packing' in the 'Testing the
installed valve' section). If the packing leaks continuously,
replace the packing (see section 9.4.2).
The control valve was checked by SAMSON
before it left the factory.
− Certain test results certified by SAMSON
lose their validity when the valve is
opened. Such testing includes seat leakage
and leak tests.
− The product warranty becomes void if
service or repair work not described in
these instructions is performed without
prior agreement by SAMSON's after-sales
service.
−
Only use original spare parts by
SAMSON, which comply with the original
specifications.
9.1
Periodic testing
Depending on the operating conditions,
check the valve at certain intervals to prevent
a possible failure before it can occur. Opera-
tors are responsible for drawing up an in-
spection and test plan.
Our after-sales service can support you in
drawing up an inspection and test plan for
your plant.
Note
Tip
Summary of Contents for 3256
Page 22: ...3 8 EB 8065 EN...
Page 44: ...5 18 EB 8065 EN...
Page 70: ...12 2 EB 8065 EN...
Page 72: ...13 2 EB 8065 EN...
Page 74: ...14 2 EB 8065 EN...
Page 75: ...EB 8065 EN 14 3...
Page 76: ...14 4 EB 8065 EN...
Page 80: ...15 4 EB 8065 EN...
Page 81: ......
Page 82: ......
Page 83: ......