EB 8060 EN
4-5
Shipment and on-site transport
4.4 Storing the valve
Risk of valve damage due to improper stor-
age.
Î
Observe the storage instructions.
Î
Avoid long storage times.
Î
Contact SAMSON in case of different
storage conditions or longer storage
times.
We recommend regularly checking the con-
trol valve and the prevailing storage condi-
tions during long storage periods.
Storage instructions
− Protect the control valve against external
influences (e.g. impact).
− Secure the valve in the stored position
against slipping or tipping over.
−
Do not damage the corrosion protection
(paint, surface coatings). Repair any
damage immediately.
− Protect the control valve against moisture
and dirt. Store it at a relative humidity of
less than 75 %. In damp spaces, prevent
condensation. If necessary, use a drying
agent or heating.
− Make sure that the ambient air is free of
acids or other corrosive media.
− The permissible storage temperature of
standard control valves is –20 to +65 °C.
Contact our after-sales service for the
storage temperatures of other valve ver-
sions.
− Do not place any objects on the control
valve.
Special storage instructions for elastomers
Elastomer, e.g. actuator diaphragm
− To keep elastomers in shape and to pre-
vent cracking, do not bend them or hang
them up.
− We recommend a storage temperature of
15 °C for elastomers.
− Store elastomers away from lubricants,
chemicals, solutions and fuels.
Our after-sales service can provide more de-
tailed storage instructions on request.
NOTICE
!
Note
Tip
Summary of Contents for 3254
Page 22: ...3 8 EB 8060 EN...
Page 28: ...4 6 EB 8060 EN...
Page 74: ...12 2 EB 8060 EN...
Page 76: ...13 2 EB 8060 EN...
Page 78: ...14 2 EB 8060 EN...
Page 79: ...EB 8060 EN 14 3...
Page 80: ...14 4 EB 8060 EN...
Page 85: ......
Page 86: ......
Page 87: ......