G27C

 

IS G27C 0711.doc 

 

 

GB 

 
FEATURES

 

- Control unit for different type of detectors. 
- Manual or Automatic reset of Alarm. 
- Push button alarm test. 
- Adjustable alarm levels. 
- DIN-rail mounted. 
 

FUNCTION

 

At start up, the LED ”ON” will be lit and a process to activate the 
detector will start in the control unit. 
 
When the LED "

Active

" is lit the system is ready to detect a gas 

leakage. Gas leakage will first give a warning, this is indicated 
by an illuminated red LED 

”Warning”

 and the relay output will 

close. If gas concentration increases the Warning will go to 

"Alarm"

 status. This means that LED Alarm will be constantly 

lit and the alarm relay will close. Automatic or manual reset can 
be selected by a jumper. 

 
Manual reset:

 Reset of relays and LEDs by pushbutton 

”Reset”. 

Automatic reset:

 Reset of relays and LEDs will be automatic 

when the gas disappears. 

"Fault Alarm"

 will light when there is a break or a short-circuit 

in the cable or in the detector itself. 
 

INSTALLATION

 

Din rail mounted control unit. 
Connection according to wiring diagram. 
The circuit diagram to the left shows Alarm relays in position 
power off. 

NOTE

! The fault Alarm relay is normally energised (closed) and 

switches off if there is a power failure in the system. 
 
When the GD/GS/GR2.0- detector is used no calibration is 
required. When using GJ-EX or any other detector, please 
advice details when ordering. 
 

ANNUAL FUNCTION CONTROL 

Testing the system is recommended to be done at least twice a 
year. A basic function test can be made using a service tool 
(SA100) and a voltage meter. 
Extended control and calibration also requires test gas with a 
specific concentration. 
Contact us for more information. 
 

TECHNICAL DATA

 

Power supply: 

12 V AC/DC  7 W 

Sensor cable: 

4 (3)x 0.75 mm

2

  max. 50 m 

(screened) 

4 (3)x  1.5   mm

2

  max 150 m 

LED indicators: 

Alarm, Warning, Fault alarm, Active 

 and 

(Power 

On) 

Outputs: 

Alarm  24V AC/DC  1A 

 

Warning  24V AC/DC  1A 

 

Fault alarm  24 V AC/DC  1 A 

Ambient temp. 

0

0

C - 50

0

Housing: IP 

30 

Dimensions: 79x118x58mm. 

 

 

Suitable for 35mm DIN rail 

 
This product is in conformity with 
the EMC-directive 89/336/EEC. 
It fulfils the requirements of: 
SS-EN 50 081-1, ed. 1 1992 
SS-EN 50 082-2, ed. 1 1995 
 

 
 
 
 

 

 
 
Specifications subject to change. 
 

11

10

9

8

7

6

5

4

3

2

1

(-)

 

(+)

 

(M)

 

{

 

{

 

{

Auto

Manual

Test 
terminal

Warning
Alarm

Warning level

Alarm level

} GD/GS/GR-2.0 detector

 

} GJ-EX/others

 

Type of detector

Choice of reset-function is 
made by a jumper

GV-Pot

A

W

Fault 
Alarm

 

Alarm

 

Warning

 

Detector

 

Circuit diagram

 

Supply 
12 V AC or DC

 

 

 

Summary of Contents for G27C

Page 1: ...27C IS G27C 0711 doc 1 SE Instruktioner GB Instructions D Anleitungen ES Instrucciones FR Instructions G27C SE Centralenhet GB Monitoring unit D Warnanlage ES Unidad de supervisión FR Unité de détection ...

Page 2: ...G27C IS G27C 0711 doc 2 Kopplingsschema Wiring diagram Schaltplan Diagrama del cableado Schéma de câblage ...

Page 3: ...ge OBS Fellarmreläet är normalt draget vilket innebär att vid strömavbrott utgår fellarm När GD GS GR2 0 xx detektorn används krävs ingen speciell kalibrering När GJ EX eller annan detektor skall användas med G27C skall detta anges vid beställning ÅRLIG FUNKTIONSKONTROLL Detektorn bör kontrolleras minst två gånger per år Ett enkelt funktionsprov kan utföras med hjälp av en service adapter SA100 oc...

Page 4: ...relay is normally energised closed and switches off if there is a power failure in the system When the GD GS GR2 0 detector is used no calibration is required When using GJ EX or any other detector please advice details when ordering ANNUAL FUNCTION CONTROL Testing the system is recommended to be done at least twice a year A basic function test can be made using a service tool SA100 and a voltage ...

Page 5: ...ührend geschlossen und schaltet bei Stromausfall in der Anlage aus Bei Anwendung der Detektoren GD GS GR2 0 ist keine Kalibrierung erforderlich Bei Anwendung von GJ EX oder einem anderen Detektor bitte bei Bestellung Einzelheiten angeben JÄHRLICHE FUNKTIONSPRÜFUNG Die Anlage sollte mindestens zweimal jährlich einer Prüfung unterzogen werden Eine grundlegende Funktionsprüfung lässt sich mit einem S...

Page 6: ...desconectada AVISO Normalmente el relé de alarma de fallo suele tener energía cerrado y se apaga en caso de fallo de alimentación del sistema Los detectores GD GS GR2 0 no requieren calibración Cuando se utilicen los detectores GJ EX o cualquier otro se ruega especificar detalles al formular el pedido CONTROL DE FUNCIONAMIENTO ANUAL Se recomienda probar el equipo al menos dos veces al año Se puede...

Page 7: ...ormalement le relais d alarme par défaut est sous tension fermé et s éteint en cas de panne de courant du système L utilisation d un détecteur GD GS GR2 0 ne requiert aucun étalonnage En cas d utilisation d un détecteur GJ EX ou autre veuillez indiquer ces informations lors de votre commande CONTRÔLE DE FONCTIONNEMENT ANNUEL Il est recommandé de tester le système deux fois par an Un essai des fonc...

Reviews: