18
4.7
SAMON GLACIÄR app features
The
“SAMON GLACIÄR” app
lets users fully exploit the potential of the new
GLACIÄR MIDI
series gas detectors, allowing
simple and intuitive interaction with the gas detector. This simplifies configuration by using a smartphone to interface
with the
GLACIÄR MIDI
gas leakage detectors.
The
SAMON GLACIÄR app
is available on the ANDROID store and on the IOS App Store.
SAMON GLACIÄR
can be used to perform the following functions:
•
Configuration: modify alarm thresholds, configure Modbus settings, modify relay behaviour, and manage analogue output
settings
•
Maintenance: check correct functioning of the device
•
Calibration, complete with calibration report
•
Display of current gas concentration measurement and indication of alarm/fault status
4.7.1
Connecting the device via Bluetooth
Before connecting to the device via the
SAMON GLACIÄR app
, first make sure that the BLUETOOTH connection and
GEOLOCATION are enabled on the smartphone used (Android only).
Make sure that Bluetooth mode has been activated on the
GLACIÄR MIDI
using the magnetic key, as described in the
previous chapter.
Open the
SAMON GLACIÄR app
(previously downloaded); the following screen is displayed.
Login screen
Bluetooth connection screen
Select:
•
Operator, to continue displaying the gas detector variables
and parameters.
•
Technician, for password access and the possibility to set the
parameters and variables.
The password to unlock the device is
2222
.
If all the functions described above have been enabled on the
smartphone and the GLACIÄR MIDI is in Bluetooth mode, the
available devices are shown on the app screen. If this is not the case,
touch the app screen to refresh the display.
Verify that the serial number on the label of the device being
connected matches the one displayed on the screen.
Select the correct device and verify correct connection. The
Bluetooth symbol at the top right changes from red to green.
Summary of Contents for FLSJ1263A
Page 1: ...GLACI R MIDI Gas Leakage Detector for commercial and industrial applications USER MANUAL...
Page 5: ...5 2 2 Physical dimensions Built in version Remote version...
Page 29: ...29 5 4 1 Diagram of the calibration procedure...
Page 30: ...30 5 4 2 Operation of the registers for calibration...
Page 37: ...37...
Page 38: ...38...
Page 39: ...39...
Page 40: ...40 Manufactured by Samon AB Modemgatan2 S 23539Vellinge Sweden www samon se...