A warning circuit monitors the operational condition of the fans.  In case of a fan failure, a 
buzzer will sound and the red LED indicating “FAN FAILURE” will light up.  The unit should be 
switched off immediately and the defective fan should be replaced.  

NEVER LOAD THE UNIT 

WHEN THERE IS AN AUDIBLE ALARM AND THE FAN FAILURE LED  IS ILLUMINATED.

 

 

The 2 fans are rated for 12 V nominal and are powered from the output voltage of the modules. 
A small Printed Circuit Board (PCB) located on the right corner towards the back of the unit is 
used to monitor the fans for abnormal operating conditions viz. open circuit or overload condi-
tion due to obstructed rotor.  

 
FRONT PANEL CONTROLS AND INDICATORS 
 

The following controls and indicators are provided on the front panel : 
 

1A. POWER ON/OFF SWITCH. 

 The rocker switch will illuminate when switched on.   

 

1B. BREAKER. 

A circuit breaker provides protection on the input side against overload 

 

2. VOLTMETER / AMMETER.  

A combined voltmeter and ammeter are provided. The function 

can be switched by the Volt / Amp switch (3) 

 
3.   METER CHANGE-OVER SWITCH.  

Switches the combined meter between ammeter and 

voltmeter 

 
4.   L.E.D “ PSM STATUS (1 to5)”.  

During normal operation, the green LED of each 

P

ower 

S

upply 

M

odule 

(PSM) 

will light.

 

In case a power supply module (PSM) fails, its corresponding 

LED will go off. LED 1 is for the left most module (near the on/off switch) 

 
5.    L.E.D “FAN FAILURE ”:  

In case of fan failure, this red LED lights up and a buzzer is 

sounded. 

 
 
 
 

 
 
 
 
 
 
 
REAR PANEL CONNECTORS 

 
The following output connectors have been provided (Not shown). 
 

 

1. 

Load+ (Positive), Load- (Negative) LOAD CONNECTORS.  
For connecting to the D.C. Load 

2. 

(Positive), Battery- (Negative) BATTERY CONNECTORS. 
For connecting external battery for un-interrupted D.C. power to the load. 

 

 

 

 

1B. 

4. 

3. 

1A. 

5. 

2. 

4. 

Summary of Contents for SEC-40BRM-220

Page 1: ...0BRM 220 SEC 80BRM 220 SEC 100BRM 220 Please read this manual before operating your power supply INSTALLATION OPERATING MANUAL EXPANDABLE DC POWER SUPPLY 230V AC INPUT N 1 DC Power System with Battery...

Page 2: ...RIES FOR BACKUP EXPAND OUTPUT POWER BY ADDING POWER MODULES UP TO 100 AMPS CONTINUOUS POWER VOLT AMPERE METER OPERATION STATUS L E D FAN FAILURE ALARM AND WARNING L E D REMOTE MONITORING AND INDICATIO...

Page 3: ...re 3 Front panel controls and indicators 4 Rear panel controls 4 5 Protections 5 Installation and operation 6 Operation of battery back up 7 Output voltage adjustment 8 9 Installation and removal of m...

Page 4: ...2 POLE 2 WIRE RECEPTACLE THAT HAS NO GROUNDING REPLACEMENT OF POWER CORD PLUG THE POWER CORD IS PROVIDED WITH A MOULDED STANDARD EUROPEAN 2 POLE 3 WIRE GROUNDING PLUG SCHUKO 250V 16A THE PLUG MAY BE R...

Page 5: ...ELOW TO CONNECT ANY DEVICE TO THE POWER SUPPLY THESE CABLE SIZES ARE VALID WHEN THE DEVICE IS WITHIN 6 FT DIS TANCE FROM THE POWER SUPPLY THICKER WIRING WILL BE REQUIRED FOR LONGER DISTANCES THINNER W...

Page 6: ...PSM is required to be interconnected with one another to a common SHARE BUS through a pair of parallel pins marked JUMP 1 and jumper wires Fig 1 and 2 For proper operation of the current share control...

Page 7: ...CH The rocker switch will illuminate when switched on 1B BREAKER A circuit breaker provides protection on the input side against overload 2 VOLTMETER AMMETER A combined voltmeter and ammeter are provi...

Page 8: ...omatically once the short circuit condition is removed CURRENT LIMITING The unit will enter this mode when the load tries to draw more than the limiting values of currents as shown in the specificatio...

Page 9: ...n the unit by pressing the power on off switch to on position The switch will be illuminated confirming that input power is available 8 A short beep may be generated by the temperature fault alarm cir...

Page 10: ...D will be as follows At no external load Approx 14V At 10 A load Approx 13 8V At loads 10A Approx 13 8V minus 5mV per Amp above 10A THE BATTERY SHOULD BE LOCATED IN A WELL VEN TILATED AREA TO SAFELY D...

Page 11: ...utput voltage of the module The adjustment range is 13 8 V to 14 6 V For the forced current share control to work properly it is important that the output voltage of each module connected in parallel...

Page 12: ...C connectors for PSM 2 and connect them to PSM 2 Now only PSM 2 can energize Switch on the power supply Only PSM No 2 will operate Adjust the output voltage of this module to the desired value with th...

Page 13: ...ector Connection to the opto coupler PCB and on ward to the D Sub connector for remote indication is made using color coded pair of wires for each of the 5 modules Please see the colour code for PSM 1...

Page 14: ...RE THAT THERE IS NO BREAK IN THE SHARE BUS DAISY CHAIN AND THAT ALL THE JUMP1 TERMINALS ARE INTERCONNECTED 6 The module can now be removed TROUBLE SHOOTING POWER ON OFF SWITCH DOES NOT LIGHT WHEN SWIT...

Page 15: ...n LED would extinguish or flash Reduce the load drawn to a value less than the combined maximum rated output of the working modules If the voltage does not rise to the rated voltage of 13 65 V to 13 3...

Page 16: ...io Filters are used to limit the noise to acceptable level 3 Switching power supplies are also recipients of radio interference The nor mal operation of the power supply can be disturbed due to RF noi...

Page 17: ...outlet circuits receptacles In such cases disconnect devices connected to the other AC outlet circuits receptacles served by this GFCI 6 Following additional guidelines may be followed to reduce the...

Page 18: ...the earth ground through the earth ground pin of the AC power outlet receptacle Avoid connecting referencing the DC negative output terminal of the power supply to the earth ground e Connect a 1 4 wav...

Page 19: ...T LIMIT 48A 72A 96A 120A OUTPUT RIPPLE PEAK TO PEAK 150mV OUTPUT NOISE PEAK TO PEAK 1V 0 9V 0 8V 0 7V COOLING FORCED AIR 2 FANS OPERATING TEMPERATURE 0 TO 40 C PROTECTIONS SHORT CIRCUIT YES CURRENT LI...

Page 20: ...e and Negative output BUS Bars L N L line and N neutral terminals for 120V 60 Hz input power supply wires LED 1 Terminal for ON status for opto isolated remote indication LED 2 Terminal for LED PSM st...

Page 21: ...socket for the missing sandwiched module s should be shorted by inserting a shorting link to pre vent a break in the daisy chain Fig 3 Jump 1 Jump 1 Jump 1 Jump 1 Jump 1 1 Female socket terminal of t...

Page 22: ...y the Warrantor Any attempt to remedy the defect by anyone other than the Warrantor shall render this warranty void There shall be no warranty for defects or damages caused by faulty installation or h...

Page 23: ...Attach copy of receipt here for your records Date purchased Additional notes Purchased from 20...

Page 24: ...Thank you for purchasing a Samlex power supply product Samlex America Inc 110 17 Fawcett Road Coquitlam B C V3K 6V2 Canada SEC 40 60 80 100BRM _230_Feb2008...

Reviews: