24 | SAMLEX AMERICA INC.
failure to Start Some Devices on Load
Some high capacitance loads like Compact fluorescent Lamp (CfL) or Switched Mode
Power Supply (SMPS) will shut down the inverter under overload condition if the inverter
is switched oN with these loads in oN condition. However, if these loads are switched
off first and switched oN only after around 10 sec after the inverter is switched oN (as
already recommended under switching oN procedure), the inverter may not shut down.
Hence, do not switch oN the inverter with such loads in oN condition.
monitoring of operational Status & protections
Normal / abnormal behavior can be monitored by observing Green LeD (8, Inverter), Yel-
low LED (6, Input Fault), Red LED (9, Fault) and Buzzer. Details are given in
Table 6.1 below:
table 6.1 protections and monitoring: inverter is Supplying power
operating
condition/
protection
threshold/
reason
Green
LeD (8,
inverter)
yeLLoW
LeD (6,
input
fault)
reD
LeD (9,
fault)
Buzzer
remedy/reset
Normal
-
ON
OFF
OFF
OFF
-
Low DC Input
Alarm
10.8V ± 0.3V
ON
OFF
OFF
ON
Check battery voltage and
input voltage drop.
Auto reset when voltage
> 10.5 V ± 0.3V.
No Output
due to Low DC
Input Voltage
shutdown
10.5V ± 0.3V
OFF
ON
OFF
ON
Check battery voltage and
input voltage drop.
Auto reset when voltage
rises to >11.5V.
No output due
to High DC
Input Voltage
Shut Down
15.5 ± 0.2V
OFF
ON
OFF
OFF
Check charger voltage.
Auto reset when voltage
< 15.5V.
No Output
due to High
Temperature
Shut Down
Internal hot
spot > 88
°
C
to 115
°
C
OFF
ON
OFF
OFF
Check ambient tempera-
ture, fan and loss of cool
replacement air .
Auto reset when hot spot
cools down 10
°
C to 15
°
C
below the threshold.
SECTION 6 |
Protections Monitoring
& Troubleshooting