12 | SAMLEX AMERICA INC.
SAMLEX AMERICA INC. | 13
Table 2.1 provides a list of some common AC appliances / devices that require high, short
duration surge of power during start up. An “Inverter Sizing Factor” has been recom-
mended against each which is a Multiplication Factor to be applied to the Maximum
Continuous Running Power Rating (Active Power Rating in Watts) of the AC appliance
/ device to arrive at the Maximum Continuous Running Power Rating of the inverter
(Multiply the Maximum Continuous Running Power Rating (Active Power Rating in
Watts) of the appliance / device by recommended Sizing Factor to arrive at the Maxi-
mum Continuous Running Power Rating of the inverter.
TABLE 2.1: INVERTER SIZING FACTOR
Type of Device or Appliance
Inverter
Sizing Factor
(See note 1)
Air Conditioner / Refrigerator / Freezer (Compressor based)
5
Air Compressor
4
Sump Pump / Well Pump / Submersible Pump
3
Dishwasher / Clothes Washer
3
Microwave (where rated output power is the cooking power)
2
Furnace Fan
3
Industrial Motor
3
Portable Kerosene / Diesel Fuel Heater
3
Circular Saw / Bench Grinder
3
Incandescent / Halogen / Quartz Lamps
3
Laser Printer / Other Devices using Infrared Quartz Halogen Heaters
4
Switch Mode Power Supplies (SMPS): no Power Factor correction
2
Photographic Strobe / Flash Lights
4 (See Note 2)
NOTES FOR TABLE 2.1
1. Multiply the Maximum Continuous Running Power Rating (Active Power Rating in
Watts) of the appliance / device by the recommended Sizing Factor to arrive at the
Maximum Continuous Running Power Rating of the inverter.
2. For photographic strobe / flash unit, the Surge Power Rating of the inverter should be
> 4 times the Watt Sec rating of photographic strobe / flash unit.
SECTION 2 |