DC-DC Converter Manual

   |   3

IDC-360 | 

USER ManUal

MoDEl 

no.

InpUt VoltaGE 

RanGE (VDC)

MaX InpUt 

CURREnt (a)

oUtpUt 

VoltaGE (VDC)

oUtpUt 

CURREnt (a)

IDC-360A-12

9 - 18

<40

12.5

30

IDC-360B-12

20 - 35

<30

12.5

30

IDC-360C-12

30 - 60

<20

12.5

30

IDC-360D-12

60 - 120

<10

12.5

30

IDC-360A-24

9 - 18

<40

24.5

15

IDC-360B-24

20 - 35

<30

24.5

15

IDC-360C-24

30 - 60

<20

24.5

15

IDC-360D-24

60 - 120

<10

24.5

15

IDC-360B-48

20 - 35

<30

48.0

7.5

IDC-360C-48

30 - 60

<20

48.0

7.5

no loaD CURREnt DRaW

< 25 mA

InpUt to oUtpUt ISolatIon

Yes. > 400V RMS

oUtpUt RIpplE & noISE

< 50 mV RMS

pEaK EffICIEnCY

85%

CoolInG

By temperature controlled fan

opERatInG tEMpERatURE 

anD DE-RatInG

-20 to +30oC / -4oF to 86oF   

(De-rate linearly to zero at 70oC / 158oF)

HUMIDItY, non-ConDEnSInG

Max 95%

pRotECtIonS

Overload / short circuit on the output side; 

Over voltage on the output side; Over voltage / 

transients on the input side; Reverse polarity on 

the input side; Over heating

SafEtY anD EMC StanDaRDS

eMissiONs 

EN55014-1

iMMuNiTy 

EN55014-2

AuTOMOTiVe DireCTiVe 

UN Regulation ECE R10-4

InpUt / oUtpUt ConnECtIonS 

Quick Connect ; Male, 6.3 mm /  

1/4" flat blade

DIMEnSIonS (W x D x H) 

132.8 x 190.5 x 83 mm / 5.23 x 7.5 x 3.27 in

WEIGHt 

1.4 Kg / 3.1 lb 

    NOTe: specifications are subject to change without notice

 

DIMEnSIonS & laYoUt

1

2

3

4

6

5

83

mm

91mm

6. Fan suction openings
7. Fan
8. Fan exhaust openings
NOTE: Terminals 1 to 4: Quick Connect - Male,
             6.3 mm / 1/4” flat blade

LEGEND

1. Input +
2. Input -
3. Output -
4.
5. Chassis Ground

}

At the back

(not shown)

Fig. 2 Layout (Front View)

Height: 83 mm

5

190.5

181

132.8

91

Note: All measurements are in mm.

FRONT 

SIDE

BACK 

SIDE

Fig 1. Dimensions (Bottom View)

SpECIfICatIonS

taBlE 1.  

exTerNAL iNPuT siDe Fuse & WiriNg 

MoDEl 

naME 

fUSE SpECS

WIRE SIZE (3 ft from Battery) 

(SEE notE 1 BEloW)

IDC-360A-12, 24

32V, 40A

AWG#10

IDC-360B-12, 24, 48

32V, 30A

AWG#14

IDC-360C-12, 24, 48

80V, 20A

AWG#16

IDC-360D-12, 24

125V, 10A

AWG#22

taBlE 2.  

exTerNAL OuTPuT siDe Fuse & WiriNg 

MoDEl 

naME 

fUSE SpECS

WIRE SIZE (3 ft from Battery) 

(SEE notE 1 BEloW)

IDC-360A-12

32V, 30A

AWG#10

IDC-360B-12

32V, 30A

AWG#10

IDC-360C-12

32V, 30A

AWG#10

IDC-360D-12

32V, 30A

AWG#10

IDC-360A-24

32V, 15A

AWG#16

IDC-360B-24

32V, 15A

AWG#16

IDC-360C-24

32V, 15A

AWG#16

IDC-360D-24

32V, 15A

AWG#16

IDC-360B-48

58V, 7.5A

AWG#22

IDC-360C-48

58V, 7.5A

AWG#22

notES foR taBlE 1 anD 2:

a)   Wire sizes shown are based on 90oC / 194oF wire temperature rating and 

2% voltage drop over distance of 3' from battery or load for current = 

Amp rating of the fuse.

b)   For distances > 3', use thicker wires to limit voltage drop to <2% for 

current = Amp rating of the fuse.

tERMInatIon of ConnECtInG WIRES:

c)  Use 6.3mm / 1/4" "Quick Connect", Female mating terminal on the 

connecting wiring. This type of terminal is available for maximum wire 

size of AWG #10. When using wires thicker than AWG #10, you may 

terminate the wire as follows:

 

•   Use 6.3mm / 1/4" "Quick Connect" Female matting connector 

(AWG #10 size)

 

•   Use around 2" piece of AWG #10 wire and crimp the connector to one 

end Solder / splice the other end of AWG #10 wire to wire the thicker wire

Use of short length of 2" of smaller AWG #10 wire will not increase voltage 

drop appreciably.