DC-DC Converter Manual
| 3
IDC-360 |
USER ManUal
MoDEl
no.
InpUt VoltaGE
RanGE (VDC)
MaX InpUt
CURREnt (a)
oUtpUt
VoltaGE (VDC)
oUtpUt
CURREnt (a)
IDC-360A-12
9 - 18
<40
12.5
30
IDC-360B-12
20 - 35
<30
12.5
30
IDC-360C-12
30 - 60
<20
12.5
30
IDC-360D-12
60 - 120
<10
12.5
30
IDC-360A-24
9 - 18
<40
24.5
15
IDC-360B-24
20 - 35
<30
24.5
15
IDC-360C-24
30 - 60
<20
24.5
15
IDC-360D-24
60 - 120
<10
24.5
15
IDC-360B-48
20 - 35
<30
48.0
7.5
IDC-360C-48
30 - 60
<20
48.0
7.5
no loaD CURREnt DRaW
< 25 mA
InpUt to oUtpUt ISolatIon
Yes. > 400V RMS
oUtpUt RIpplE & noISE
< 50 mV RMS
pEaK EffICIEnCY
85%
CoolInG
By temperature controlled fan
opERatInG tEMpERatURE
anD DE-RatInG
-20 to +30oC / -4oF to 86oF
(De-rate linearly to zero at 70oC / 158oF)
HUMIDItY, non-ConDEnSInG
Max 95%
pRotECtIonS
Overload / short circuit on the output side;
Over voltage on the output side; Over voltage /
transients on the input side; Reverse polarity on
the input side; Over heating
SafEtY anD EMC StanDaRDS
eMissiONs
EN55014-1
iMMuNiTy
EN55014-2
AuTOMOTiVe DireCTiVe
UN Regulation ECE R10-4
InpUt / oUtpUt ConnECtIonS
Quick Connect ; Male, 6.3 mm /
1/4" flat blade
DIMEnSIonS (W x D x H)
132.8 x 190.5 x 83 mm / 5.23 x 7.5 x 3.27 in
WEIGHt
1.4 Kg / 3.1 lb
NOTe: specifications are subject to change without notice
DIMEnSIonS & laYoUt
1
2
3
4
6
5
83
mm
91mm
6. Fan suction openings
7. Fan
8. Fan exhaust openings
NOTE: Terminals 1 to 4: Quick Connect - Male,
6.3 mm / 1/4” flat blade
LEGEND
1. Input +
2. Input -
3. Output -
4.
5. Chassis Ground
}
At the back
(not shown)
Fig. 2 Layout (Front View)
Height: 83 mm
5
190.5
181
132.8
91
Note: All measurements are in mm.
FRONT
SIDE
BACK
SIDE
Fig 1. Dimensions (Bottom View)
SpECIfICatIonS
taBlE 1.
exTerNAL iNPuT siDe Fuse & WiriNg
MoDEl
naME
fUSE SpECS
WIRE SIZE (3 ft from Battery)
(SEE notE 1 BEloW)
IDC-360A-12, 24
32V, 40A
AWG#10
IDC-360B-12, 24, 48
32V, 30A
AWG#14
IDC-360C-12, 24, 48
80V, 20A
AWG#16
IDC-360D-12, 24
125V, 10A
AWG#22
taBlE 2.
exTerNAL OuTPuT siDe Fuse & WiriNg
MoDEl
naME
fUSE SpECS
WIRE SIZE (3 ft from Battery)
(SEE notE 1 BEloW)
IDC-360A-12
32V, 30A
AWG#10
IDC-360B-12
32V, 30A
AWG#10
IDC-360C-12
32V, 30A
AWG#10
IDC-360D-12
32V, 30A
AWG#10
IDC-360A-24
32V, 15A
AWG#16
IDC-360B-24
32V, 15A
AWG#16
IDC-360C-24
32V, 15A
AWG#16
IDC-360D-24
32V, 15A
AWG#16
IDC-360B-48
58V, 7.5A
AWG#22
IDC-360C-48
58V, 7.5A
AWG#22
notES foR taBlE 1 anD 2:
a) Wire sizes shown are based on 90oC / 194oF wire temperature rating and
2% voltage drop over distance of 3' from battery or load for current =
Amp rating of the fuse.
b) For distances > 3', use thicker wires to limit voltage drop to <2% for
current = Amp rating of the fuse.
tERMInatIon of ConnECtInG WIRES:
c) Use 6.3mm / 1/4" "Quick Connect", Female mating terminal on the
connecting wiring. This type of terminal is available for maximum wire
size of AWG #10. When using wires thicker than AWG #10, you may
terminate the wire as follows:
• Use 6.3mm / 1/4" "Quick Connect" Female matting connector
(AWG #10 size)
• Use around 2" piece of AWG #10 wire and crimp the connector to one
end Solder / splice the other end of AWG #10 wire to wire the thicker wire
Use of short length of 2" of smaller AWG #10 wire will not increase voltage
drop appreciably.