SECTION 8 |
Installation
42
8.8 INVERTER POWER ON/OFF THROUGH EXTERNAL BY-PASS OR
VOLTAGE SIGNAL
Powerswitch must be at EXT position to enable this function.
EXT. SW.
S + -
BY-PASS:
Connect jumper between ‘S’ to ‘–’ to externally
by-pass ON/OFF.
Voltage signal:
Connect 10V~33VDC and between ‘+’ to ‘-’
to turn the inverter ON/OFF.
8.9 DIP SWITCH SETTING POWERSAFE AND FREQUENCY
Turn off the inverter before adjusting the Dip Switch settings.
PS F
PS: Normal mode / Power saving mode switch:
Normal mode
(switch 1 at upper position).
Power saving mode
(switch 1 at lower position):
• Entering power saving mode when no load is connected
to the inverter for 5 seconds.
• Entering normal inverter operation when load is
higher than:
- 10 Watt for SWI 400-12/24 and SWI 700-12/24
- 30 Watt for SWI 1100-12/24 and SWI 1600-12/24
- 40 Watt for SWI 2100-12/24
F: Frequency switch:
- 50Hz (switch 2 at upper position)
- 60Hz (switch 2 at lower position)