5
Electrical connection
Attention!
The electrical connection of the equipment may only be carried out by
qualified and skilled personnel!
Attention!
It is absolutely necessary to ground the ExCam
®
series
’ housing via
the PA connection.
Attention!
Please observe the national security, installation and accident preven-
tion regulations (e.g. DIN EN 60079-14) and the safety instructions in
this User Manual, as well as the ones in the Installation Guidelines!
The delivered ExCam
®
XI410 is equipped with an electrical connection cable of the type
SKDP03-T. The maximum transmission range from the camera to the next active network
interface is 100 m and can be specified by the client. The user is NOT authorised to carry
out any electrical connection work inside the pressure-resistant enclosure (T08).
5.1
Potential equalization
Figure 5-1 ExCam XI410 Potential equalization
Potential equalization/grounding of the camera housing is absolutely necessary, in order
to avoid static charges and thus the formation of sparks. For this purpose, a screw termi-
nal is provided at the
rear side’s bottom (see Figure 5-1). The cross-section of the poten-
tial equalization has to comply with the National Ground Rules (at least 4mm
2
).
Wiring table:
Potential
Colour (IEC 60757)
Cross-
section
Comment
PA
GN/YE
4 mm
2
(rigid)
Terminal: Slotted screw M3x0.5x5 (DIN 84)
with washer Ø3,2mm (DIN 125A),
Keep 1.2 Nm tightening torque!
Table 5-1 Potential equalization