Electrical Connection
ESS Inverter User Manual
27
Normal Load
Flow from grid
to inverter
N
N
L
CT
L
Grid
The current direction from grid to inverter is defined as positive and
current direction from inverter to grid is defined as negative.
NOTE
4.5.2
CT Connection
Before connecting to Grid, please install a separate AC breaker (not equipped) between CT and Grid.
This will ensure the inverter can be safely disconnected during maintenance.
The connection diagram of power cable of CT is as shown in the figure below:
Please attention to the Current interchanger (CT) connection. The arrow on the CT indicates the current
flow from grid to inverter. And lead the live line through the detection hole of CT.