7-1
Module 5 – Connected Fan Coil Controls
Device Configuration – Fan Coil Controls
Section 7
* Humidity:
This setting allows users to adjust the relative
humidity setpoint .
Range:
Humidifier – 20% to 50%
Dehumidifier – 40% to 80%
The ^ and v keys adjust the flashing relative humidity setpoint . Press
SELECT to choose the displayed value and move to the next setting .
* This setting is only available if the accessory parameter (P22) is set to
Humidifier (
) or Dehumidifier (
) .
Temperature Units:
Use this setting to choose between SI Metric and
US Customary temperature units .
Use the
and
keys to toggle between °C and °F . Press
SELECT to choose the flashing value and move to the next
setting .
Sensor Location:
Use this setting to choose between internal (INT)
and external (EXT) sensor location .
Use the
and
keys to toggle between INT and EXT . Press SELECT
to choose the flashing value and move to the next setting (If INT is
chosen, INT will not be displayed on the home screen) .
* Setback:
Use this setting to choose a setback temperature for heat-
ing and/or cooling .
Range:
Heat – 50-68°F (10-20°C)
Cooling – 73-90°F (23-32°C)
Use the
and
keys to change the setback temperature . Press
SELECT to choose the flashing value and move to the next setting .
* This setting is only available if the setback input parameter (P16) is
enabled .
Clock Format: This setting is used to change the clock format be-
tween 12 hour with am/pm and 24 hour .
Use the
and
keys to toggle between 12 and 24 hour clock .
Press SELECT to choose the value displayed and move on to the next
setting .
Settings Button Operation
Press
to adjust the settings in Table 7 .1 . Some of these settings are not accessible depending on the parameter
configuration listed in Appendix A . Press select to choose the current value and move to the next available setting .
Press
to exit the settings menu .