background image

 

18 

 

Fig. 12.4 Connection of temperature sensors 

Temperature  sensors  are  equipped  with 

brass  coat  with  diameter  of  6mm  and  50mm 
long.  They  should  be  installed  possibly  close  to 
the temperature measurement point. The sensors 
must  be  installed  so  that  the  brass  coat  is 
thermally insulated from the environment. 

The collector temperature sensor must be 

located  in  the  collector  tube  possibly  deep,  as 
this is conditional for correct measurement. 

The reservoir temperature sensor must be 

located in thermometric tube between the supply 
and return connectors of the collector exchanger 
pipe coil. 

The  sensors  resistance  per  temperature 

table: 

 

CT6w\CT6 

Temp. 

°C 

Min. 

Ω 

Nom. 

Ω 

Max. 

Ω 

999,7 

1000,0 

1000,3 

25 

1096,92 

1097,35 

1097,77 

50 

1193,42 

1193,97 

1194,52 

100 

1384,26 

1385,06 

1385,86 

125* 

1478,59 

1479,51 

1480,44 

150* 

1572,2 

1573,25 

1574,30 

*only for CT6w sensor 

 

13.

 

HOW TO CLOSE CASING 

To close the unit casing hook the casing cover 

with  recesses  against  the  base  insets  (shown  in 
Fig. 13.1) 

 

Fig. 13.1 Casing closing first step 

Then,  press  the  cover  in  place  indicated 

by  red  arrow  (Fig.  13.2),  until  you  clearly  hear 
the latch click. 

 

Fig. 13.2 Casing closing second step 

 
 

Summary of Contents for PCSol 150

Page 1: ...Controller PCSol 150 REVISION 1 1 SOFTWARE 1 xx 26 05 2015 FOR SOLAR COLLECTORS INSTALLATION AND OPERATION MANUAL...

Page 2: ......

Page 3: ...diagram of connections 16 12 1 1 Use of connectors 17 12 1 2 Power supply connection 17 12 1 3 Temperature sensor connection 17 13 HOW TO CLOSE CASING 18 14 FUSE REPLACEMENT 19 15 TROUBLESHOOTING 20 L...

Page 4: ...c system to which the controller is connected must be protected with a cut out device suitable for expected loads Never use the controller when its casing is damaged In any case do not alter the contr...

Page 5: ...and electronic products disposal system It is recommended to process in accordance with local regulations and not to dispose used products to household garbage containers Proper disposal of outdated...

Page 6: ...6...

Page 7: ...OPERATING MANUAL PCSol 150...

Page 8: ...long with the temperature rise Measured temperature is shown with the step of 10 C for T1 sensor collector s temperature and 5 C for T2 sensor DHW reservoir temperature Subsequent segments of the indi...

Page 9: ...llector temperature TCOLmin move the cursor to the indicator with sun symbol Press the knob sun symbol will start fast blinking to enter value editing mode You may change the value by turning the knob...

Page 10: ...ted by illumination of the sun symbol indicator When the collector temperature drops two degrees below minimal temperature preset the sun symbol will go off and the controller will disable the collect...

Page 11: ...n interruption Alarm on incorrect operation or damage to T2 sensor Signals interruption in T2 sensor circuit Check if the sensor is not e g off the unit or the connecting wire is cut Collector pump op...

Page 12: ...roller off the pump operation will be stopped 9 1 Test of unit When switched on the unit undergoes some testing At the time the display shows alternately the testing screen and the software version Te...

Page 13: ...INSTALLATION MANUAL PCSol 150...

Page 14: ...the set Controller PCSol 150 Temperature sensor T1 CT6w Temperature sensor T2 CT6 Installation and operating manual 1 pc 1 pc 1 pc 1 pc 11 INSTALLATION The controller is designed for operation in the...

Page 15: ...ust and water access is prevented Permissible operating temperature is not exceeded 40 C for controller Air exchange inside casing is allowed Access to dangerous parts is disabled Electrical installat...

Page 16: ...in sections 12 1 2 12 1 3 Presented hydraulic diagram will not replace central heating technical design and may be used only for informative purposes Collector and hot water reservoir must be install...

Page 17: ...act surfaces with temperatures that exceed the cables operating temperature limits The controller has no PE protective connector because the controller itself does not require grounding PE terminals o...

Page 18: ...r must be located in thermometric tube between the supply and return connectors of the collector exchanger pipe coil The sensors resistance per temperature table CT6w CT6 Temp C Min Nom Max 0 999 7 10...

Page 19: ...t means that the fuse is burnt and must be replaced For the unit use sub miniature slow blow fuse 1 25A compliant to IEC 60127 and with maximum switching current not lower than 100A Example of such fu...

Page 20: ...Collector pump capacity is too low pump is not able to transfer heat to reservoir exchanger 3 Temperature preset for reservoir has been reached and controller has disabled the pump Collector pump is...

Page 21: ...Presented drawing is in 1 1 scale and it may be helpful during installation You may cut off this page and use to mark installation place Fig 15 1 Casing drawing for installation aid...

Page 22: ......

Page 23: ......

Page 24: ...SALUS Controls Made in Poland...

Reviews: