background image

APPLICATION

COSFI

APPLICATION

COSFI

LANGUAGE

ENGLISH   V3.0

LANGUAGE

ENGLISH   V3.0

LANGUE

FRANCAISE   V3.0

LINGUA

ITALIANO  V3.0

APPLICATION

SEWAGE

APPLICATION

CLEAN    WATER

APPLICATION

4-20mA  bar

APPLICATION

4-20mA  metri

PRESSING IT FOR MORE THAN 1s YOU GO OUT

OF THE SETUP AND THE PARAMETERS

ARE STORED IN THE MEMORY 

PRESSING IT YOU WILL SEE THE REMAINING PART OF THE PARAMETERS
THAT CAN BE SET ACCORDING TO THE APPLICATION CHOSEN:
COS

φ

 = SEE CHAPTER 5.2

CLEAN WATER = SEE CHAPTER 5.3
SEWAGE = SEE CHAPTER 5.4
4-20mA bar = SEE CHAPTER 5.5
4-20mA metres = SEE CHAPTER 5.6

COSFI  <  0.45

ENTER   MANUALLY

COSFI  >  1.00

ENTER    MANUALLY

THE COS

φ

 MEASURED 

IS LESS THAN 0.45

(POSSIBLE DRY

RUNNING)  

It is used to scroll forward through the setup pages
It is used to increase the value of a parameter

It is used to scroll back through the setup pages
It is used to reduce the value of a parameter

Pressed it allows to enter the selected parameter

Pressed confirms the set value

POSSIBLE ANOMALIES DURING THE AUTO-LEARNING PHASE

}

 SETUP   PRESS

PAG   +   MAN      10s

+

IGNITION

CONTROL PANEL

AUTO - LEARNING  

ENTER     TO    START

AUTO - LEARN.   0 %

CF    0.80                             13.2 A

AUTO - LEARNING

COMPLETED

5.1 Fast programming

5. PROGRAMMING

Pressed it exits the parameter 

ON

IN THIS STAGE THE

MOTHERBOARD STARTS

FOR APPROXIMATELY 30s

THE MOTOR RECORDING

THE PARAMETERS

AUTOMATICALLY

  

NO     LOAD

MAXIMUM    CURRENT

>    --  A

THE MOTHERBOARD

DOES NOT DETECT

ANY CONNECTED

MOTOR 

THE MOTHERBOARD HAS

CORRECTLY PERFORMED

THE AUTO-LEARNING

PROCEDURE

   

THE ABSORBED

CURRENT EXCEEDS

THE MAXIMUM

ALLOWED THRESHOLD

THE COS

φ

 MEASURED 

IS MORE THAN 1.00

(COS

φ

 READING 

ANOMALY)  

28

Summary of Contents for MULTIPLUS 1 SA684 Series

Page 1: ...N AND INSTALLATION MANUAL Direct starting electronic control panel 1 motor for clean water and sewage with display and general disconnecting switch with door lock rev 6 11 01 2023 MULTIPLUS 1 SA684 xx...

Page 2: ...programming 6 General functioning of the control panel 6 1 General functioning 6 2 Application cos 6 3 Application clean water 6 4 Application sewage 6 5 Application 4 20mA bar 6 6 Application 4 20mA...

Page 3: ...t If necessary substitute the various components only with those having the same characteristics and components as the originals 1 GENERAL INSTRUCTIONS FOR INSTALLING 2 WARNINGS ELECTRIC SHOCKS Risk o...

Page 4: ...Float switch for clean water Level probe 1 INPUT 2 INPUTS KLIX1 COM COM MIN MAX KLIX1 G MIN COM 2 START STOP COM MIN MAX CLEAN WATER DRY RUNNING COS KLIX1 COM MIN MAX G MAX2 G ALAR COM COM COM MIN MI...

Page 5: ...tive probe 4 20mA Below are some practical examples of applications that can be implemented with the MULTIPLUS 1 control panel 4 20mA bar 5 STOP START KLIX1 KLIX1 G MIN G MAX1 G ALAR G ALAR COM COM AL...

Page 6: ...2 5 mm M3 0 5Nm 8 3 mm PIEZORESISTIVE LEVEL TRANSMITTER 4 20mA WIRING PRESSURE TRANSDUCER WIRING BROWN WHITE KEY 1 2 LEVEL PROBES OR MINIMUM FLOAT SWITCH 3 4 LEVEL PROBES OR MAX1 FLOAT SWITCH 5 6 MAX...

Page 7: ...0 5Nm 8 3 mm L1 L2 L3 U V W M 3 MOTOR POWER SUPPLY 400 Vac 50 60 Hz 4 2 Wiring diagram SA687 xx 4 WIRING DIAGRAMS KEY 3 4 LEVEL PROBES OR MAX1 FLOAT SWITCH 1 2 LEVEL PROBES OR MINIMUM FLOAT SWITCH 9 1...

Page 8: ...oll forward through the setup pages It is used to increase the value of a parameter It is used to scroll back through the setup pages It is used to reduce the value of a parameter Pressed it allows to...

Page 9: ...AND G MAX OPEN ENABLE MOTOR EXTERNAL COMMAND OFF IN OFF MODE THE MOTHERBOARD EXCLUDES THE CONTROL ON THE EXTERNAL COMMAND 5 1 5 PROGRAMMING 29 THE MOTHERBOARD AUTOMATICALLY CALCULATES THE WAITING FILL...

Page 10: ...CHAPTER 5 7 BY PRESSING IT YOU RETURN TO THE FIRST SETUP SCREEN SEE CHAPTER 5 7 PRESSING IT FOR MORE THAN 1s YOU GO OUT OF THE SETUP AND THE PARAMETERS ARE STORED IN THE MEMORY PRESSING IT FOR MORE T...

Page 11: ...MUM PRESSURE OFF MINIMUM PRESSURE OFF IT IS USED TO SET THE REQUIRED PRESSURE BELOW WHICH THE MOTOR STOPPED AT THE MOTOR STARTING THIS PARAMETER IS BYPASSED FOR 1 MINUTE MINIMUM PRESSURE 0 5bar OFF EX...

Page 12: ...EVEL 1 00 m RANGE 0 10 24 95m ALARM LEVEL 1 00m ALARM LEVEL 1 00m IT IS USED TO SET THE WATER LEVEL ABOVE WHICH THE MOTHERBOARD ENABLES THE ALARM OUTPUT RANGE 1 0 25 0m RANGE 0 05 24 9m IT IS USED TO...

Page 13: ...DICATES THAT THE MINIMUM CURRENT VALUE HAS BEEN SET MANUALLY MINIMUM CURRENT OFF AUT INDICATES THAT THE MINIMUM CURRENT VALUE HAS BEEN SET WITH THE AUTO LEARNING EXCLUDING THE COS APPLICATION 5 1 5 PR...

Page 14: ...VOLTAGE BY PRESSING IT YOU RETURN TO THE FIRST SETUP SCREEN SEE CHAPTER 5 1 5 PROGRAMMING 34 PRESSING IT FOR MORE THAN 1s YOU GO OUT OF THE SETUP AND THE PARAMETERS ARE STORED IN THE MEMORY OFF EXCLU...

Page 15: ...LAYS MEASURED VOLTAGE ABSORBED CURRENT COS DETECTED OPERATING HOURS OF THE MOTOR AUTOMATIC MOTOR Cf 0 80 13 2A STOP MOTOR Cf 1 00 0 0A 400V 13 2A Cf 0 80 0h IT IS USED TO START THE MOTOR MANUALLY EXTE...

Page 16: ...ON G MAX1 CLOSED ALL OFF G ALAR OPEN ON G ALAR CLOSED 17 6 1 6 1 ONLY IN STABLE MANUAL BUTTON MODE EXTERNAL COMMAND OFF IF THE MOTHERBOARD DETECTS A DRY RUNNING CONDITION IT WILL BE POSSIBLE TO DISPL...

Page 17: ...BLE MANUAL BUTTON MODE THE FOLLOWING SCREEN DISPLAYS MEASURED VOLTAGE ABSORBED CURRENT SYSTEM PRESSURE OPERATING HOURS OF THE MOTOR IT IS USED TO START THE MOTOR MANUALLY THIS SCREEN IS DISPLAYED WHEN...

Page 18: ...0h MOT MAINTENANCE SET OFF MOT MAINTENANCE SET OFF MOT MAINTENANCE ENTER TO RESET LAST MOTOR MAINTENAN 0h LAST MOTOR MAINTENAN 500h SCREEN DESCRIPTION PERFORM MOTOR MAINTEN Exceeded the set time this...

Page 19: ...rated 8 2 Event data logger SETUP PREMI PAGE MAN 10s ON EV 12 MIN CURR MAN 8 2A 30h EV 10 MAX VOLT OFF 10h Maximum voltage Maximum motor starts per hour Minimum current The event data logger is used t...

Page 20: ...0 MAXIMUM CURRENT alarm Maximum current set on the setup less than that absorbed by the motor Motor blocked or damaged Application 4 20mA meters The displayed level in meter is wrong Clean carefully...

Page 21: ...llowing message If the voltage is within the set range and stays there for 60 seconds the motherboard will automatically reset the alarm If the motherboard detects the absence of one of the three phas...

Page 22: ...do il riciclaggio di questo prodotto contattate per cortesia il Vs ufficio locale il Vs servizio di smaltimento rifiuti domestici o il negozio dove avete acquistato questo prodotto Questo simbolo sul...

Page 23: ...i responsabilit per danni cagionati da caduta uso scorretto alterazione o negligenza 4 Questa garanzia non incide sui diritti del consumatore sanciti dalla normativa vigente Salupo S r l Salupo S r l...

Page 24: ......

Reviews: