
25
SALICRU
6.5. How to replace a faulty UPS from
the operating parallel system.
Press over the key in any UPS for more than 3 sec-
onds to shutdown all the inverters. The acoustic alarm
will beep for 3 seconds. The equipments that belong to
the current parallel system will transfer to "Bypass mode".
Put all the equipments on manual bypass. To do it re-
move the cover from manual bypass switch, which is
located at the back of each equipment and turn all the
switches to position "BYPASS".
Keep in mind that on "Bypass mode" or with the
switch on "BYPASS" position, the loads will be ex-
posed to fluctuations of voltage, frequency and mains faults
or blackouts, so in case it were possible, choose one day
with the lowest probability of faults (days without fluctua-
tions, days without storms,... ) and do it as fast as possible.
Turn the input and bypass circuit breaker protections
(TWIN/3 PRO > 10 kVA) of the distribution panel corre-
sponding to the equipment to replace to "Off".
Disconnect the communication bus of the faulty equip-
ment and all power connections too, and remove it.
Put the manual bypass switch of the new UPS, on "BY-
PASS" position. To do it remove the protection cover from
manual bypass switch, which is located at the back of the
equipment to connect.
Place the new equipment instead of the faulty one and
reconnect it. Attend the stated instructions in section
5.3.7.2, for parallel connection.
In parallel installations, the “Jumper” (cable as
bridge mode) connected from factory between the
terminals JP1 and JP2 must be removed.
• Turn "On" the circuit breakers switches corresponding to the
new UPS:
The input one from distribution panel and the one in the
UPS.
In those equipments with static bypass line (TWIN/3
PRO > 10 kVA), also the bypass one of the protection
panel and the one in the UPS.
UPSs supply output voltage from bypass. Check the screen
of the LCD from control panel in case there were any warning
or error information.
Measure the output voltage between the terminals JP1 of the
parallel system and terminals JP1 of the new UPS, to check
the voltage difference is under 1 V. In case the difference
were higher than 1 V, double check the wiring and associ-
ated instructions.
• Put back the cover of the manual bypass of each UPS.
• Press over the start up key for more than 1 second in any
of the UPSs and all of them will start up. All UPSs will transfer
to "Normal mode”.
Measure the output voltage between the terminals of the
parallel system and the output terminals of the new UPS, to
check the voltage difference is under 0,5 V. In case the differ-
ence were higher than 1 V, the UPSs have to be set (contact
with the S.T.S.).
• Press over the shutdown key in any UPS for more than 3
seconds and each one will be shutdown, supplying output
voltage through the bypass.
Turn “On” the output circuit breaker switch of the distribution
panel, corresponding to the new integrated equipment. The
complete parallel system will supply output voltage, through
the bypass.
• Remove the cover of the manual bypass in each UPS.
• Transfer the equipments with the manual bypass ("BYPASS"
position) to position "UPS". Do it in the switches of all equip-
ments.
• Put back the protection cover of the manual bypass switch
of all equipments, also check the torque of the fixing screws,
otherwise any of the limit contacts could be activated and the
manual bypass too.
• Press over the start up key for more than 1 second in any
of the UPSs and all of them will start up, finally the parallel
system will be working on "Normal mode”.
Load/s are protected by the parallel system again.
6.6. Manual Bypass Switch
(maintenance).
6.6.1. Operating principle.
Integrated manual bypass in all UPS from SLC TWIN PRO
is very useful, but a wrong use can cause irreversible conse-
quences for both the UPS and connected loads at its output.
Therefore, it is important to respect the manoeuvring over the
switch as it is stated in the following sections.
6.6.2. Transference to maintenance
bypass.
• The procedure to transfer from normal mode to maintenance
bypass is the same for a single equipment or a parallel
system, less the quantity of actions:
For a single equipment.
–
Press over the key of the UPS for more than 3 sec-
onds to shutdown the inverter. The acoustic alarm will
beep for 3 seconds. The equipment will transfer to
"Bypass mode".
For a parallel system.
–
Press over the key in any UPS for more than 3
seconds to shutdown all the inverters. The acoustic
alarm will beep for 3 seconds. The equipments that
belong to the current parallel system will transfer to
"Bypass mode".
Put all the equipment/s on manual bypass. To do it re-
move the cover from manual bypass switch, which is
located at the back of each equipment and turn all the
switch to position "BYPASS".
In parallel systems, proceed in the same way in each
equipment.
Keep in mind that on "Bypass mode" or with the
switch on "BYPASS" position, the loads will be
exposed to fluctuations of voltage, frequency and mains
faults or blackouts, so in case it were possible, choose
one day with the lowest probability of faults (days without
fluctuations, days without storms,... ) and do it as fast as
possible.
Turn the input and bypass circuit breaker protections
(TWIN/3 PRO > 10 kVA) of the equipment to "Off".
In parallel systems, proceed in the same way over the
same protections and in each equipment.
The UPS still supplies output voltage, from mains directly
or through the static bypass line (TWIN/3 PRO > 10 kVA
only), through the manual bypass of the equipment.
Summary of Contents for UPS SLC TWIN PRO series
Page 1: ...UNINTERRUPTIBLE POWER SUPPLY USER S MANUAL UPS SLC TWIN PRO series 4 20 kVA...
Page 2: ......
Page 42: ...42 USER MANUAL...
Page 43: ...43 SALICRU...