Salicru UPS SLC TWIN PRO series User Manual Download Page 25

25

SALICRU

6.5.  How to replace a faulty UPS from 

the operating parallel system.

 

ˆ

Press over the key   in any UPS for more than 3 sec-

onds to shutdown all the inverters. The acoustic alarm 

will beep for 3 seconds. The equipments that belong to 

the current parallel system will transfer to "Bypass mode".

 

ˆ

Put all the equipments on manual bypass. To do it re-

move the cover from manual bypass switch, which is 

located at the back of each equipment and turn all the 

switches to position "BYPASS".

 

ˆ

 

 Keep in mind that on "Bypass mode" or with the 

switch on "BYPASS" position, the loads will be ex-

posed to fluctuations of voltage, frequency and mains faults 

or blackouts, so in case it were possible, choose one day 

with the lowest probability of faults (days without fluctua-

tions, days without storms,... ) and do it as fast as possible. 

 

ˆ

Turn the input and bypass circuit breaker protections 

(TWIN/3 PRO > 10 kVA) of the distribution panel corre-

sponding to the equipment to replace to "Off".

 

ˆ

Disconnect the communication bus of the faulty equip-

ment and all power connections too, and remove it.

 

ˆ

Put the manual bypass switch of the new UPS, on "BY-

PASS" position. To do it remove the protection cover from 

manual bypass switch, which is located at the back of the 

equipment to connect.

 

ˆ

Place the new equipment instead of the faulty one and 

reconnect it. Attend the stated instructions in section 

5.3.7.2, for parallel connection.

 

ˆ

In parallel installations, the “Jumper” (cable as 

bridge mode) connected from factory between the 

terminals JP1 and JP2 must be removed.

•  Turn "On" the circuit breakers switches corresponding to the 

new UPS:

 

ˆ

The input one from distribution panel and the one in the 

UPS.

 

ˆ

In those equipments with static bypass line (TWIN/3 

PRO > 10 kVA), also the bypass one of the protection 

panel and the one in the UPS.

UPSs supply output voltage from bypass. Check the screen 

of the LCD from control panel in case there were any warning 

or error information.
Measure the output voltage between the terminals JP1 of the 

parallel system and terminals JP1 of the new UPS, to check 

the voltage difference is under 1 V. In case the difference 

were higher than 1 V, double check the wiring and associ-

ated instructions.

•  Put back the cover of the manual bypass of each UPS.
•  Press over the start up key   for more than 1 second in any 

of the UPSs and all of them will start up. All UPSs will transfer 

to "Normal mode”. 
Measure the output voltage between the terminals of the 

parallel system and the output terminals of the new UPS, to 

check the voltage difference is under 0,5 V. In case the differ-

ence were higher than 1 V, the UPSs have to be set (contact 

with the S.T.S.).

•  Press over the shutdown key   in any UPS for more than 3 

seconds and each one will be shutdown, supplying output 

voltage through the bypass.
Turn “On” the output circuit breaker switch of the distribution 

panel, corresponding to the new integrated equipment. The 

complete parallel system will supply output voltage, through 

the bypass.

•  Remove the cover of the manual bypass in each UPS.
•  Transfer the equipments with the manual bypass ("BYPASS" 

position) to position "UPS". Do it in the switches of all equip-

ments.

•  Put back the protection cover of the manual bypass switch 

of all equipments, also check the torque of the fixing screws, 

otherwise any of the limit contacts could be activated and the 

manual bypass too.

•  Press over the start up key   for more than 1 second in any 

of the UPSs and all of them will start up, finally the parallel 

system will be working on "Normal mode”.
Load/s are protected by the parallel system again.

6.6.  Manual Bypass Switch 

(maintenance).

6.6.1.  Operating principle.

Integrated manual bypass in all UPS from SLC TWIN PRO 
is very useful, but a wrong use can cause irreversible conse-
quences for both the UPS and connected loads at its output. 
Therefore, it is important to respect the manoeuvring over the 
switch as it is stated in the following sections.

6.6.2.  Transference to maintenance 

bypass.

•  The procedure to transfer from normal mode to maintenance 

bypass is the same for a single equipment or a parallel 

system, less the quantity of actions:

 

ˆ

For a single equipment.

 

Press over the key   of the UPS for more than 3 sec-

onds to shutdown the inverter. The acoustic alarm will 

beep for 3 seconds. The equipment will transfer to 

"Bypass mode".

 

ˆ

For a parallel system.

 

Press over the key   in any UPS for more than 3 

seconds to shutdown all the inverters. The acoustic 

alarm will beep for 3 seconds. The equipments that 

belong to the current parallel system will transfer to 

"Bypass mode".

 

ˆ

Put all the equipment/s on manual bypass. To do it re-

move the cover from manual bypass switch, which is 

located at the back of each equipment and turn all the 

switch to position "BYPASS".
In parallel systems, proceed in the same way in each 

equipment.

 

ˆ

 

Keep in mind that on "Bypass mode" or with the 

switch on "BYPASS" position, the loads will be 

exposed to fluctuations of voltage, frequency and mains 

faults or blackouts, so in case it were possible, choose 

one day with the lowest probability of faults (days without 

fluctuations, days without storms,... ) and do it as fast as 

possible.

 

ˆ

Turn the input and bypass circuit breaker protections 

(TWIN/3 PRO > 10 kVA) of the equipment to "Off".
In parallel systems, proceed in the same way over the 

same protections and in each equipment.
The UPS still supplies output voltage, from mains directly 

or through the static bypass line (TWIN/3 PRO > 10 kVA 

only), through the manual bypass of the equipment.

Summary of Contents for UPS SLC TWIN PRO series

Page 1: ...UNINTERRUPTIBLE POWER SUPPLY USER S MANUAL UPS SLC TWIN PRO series 4 20 kVA...

Page 2: ......

Page 3: ...on 5 3 9 Software 5 3 10 Considerations before starting up the connected loads 6 Operating 6 1 Commissioning 6 1 1 Controls before commissioning 6 2 Start up and shutdown of the UPS 6 2 1 Start up of...

Page 4: ...l exclusively Although we have made every effort to guarantee a com plete and accurate information in this user s manual we are not responsible for any errors or omissions that may exist The images in...

Page 5: ...installation and commissioning in an easy and ordered way without doubt Finally once the equipment is installed and operative for future requests or doubts that could arise it is recommended to keep...

Page 6: ...IEC 62040 2 Uninterruptible power supply UPS Part 2 EMC requirements The manufacturers responsibility is excluded in the event of any modification or intervention in the product by the customer s sid...

Page 7: ...due to the constant evolution of the product some discrepancies or small contradictions can arise In front of any doubt the labelling of the equipment will always prevail Figures regarding its main f...

Page 8: ...slot EPO RS 232 USB Protection cover for external batteries IEC output connectors Protection cover for manual bypass switch maintenance and output Protection cover for power blocks USB RS 232 EPO Pro...

Page 9: ...9 SALICRU Battery switch Protection cover for power blocks Batteries module for models 10 kVA Batteries module for models up to 10 kVA Battery switch Power blocks Fig 3 Rear view batteries module...

Page 10: ...ith no accessories screws and electrical cables Batteries owned by the client will be installed out from the case or cabinet of the UPS Under request it is possible to supply the acces sories screws a...

Page 11: ...low input current distortion so mains pollution is decreased Great adaptability to the worst conditions of the input mains Wide margins of the input voltage frequency range and wave shape so it is av...

Page 12: ...adaptor The big IT systems based on LANs and WANs that integrate servers with different platforms they have to include an easy way of controlling and management at the manager system dis posal This f...

Page 13: ...es type B for RCD devices and C characteristic for circuit breakers For the output load feeding C characteristic for circuit breaker Regarding the size they will be as minimum to the currents stated i...

Page 14: ...o the instructions described in this manual and charge them for 12 hours In parallel systems it is not needed to make the connection among the equipments to charge the batteries It can be treated as s...

Page 15: ...correct torque in the screws of the power blocks In installations with only one UPS the Jumper cable as bridge mode connected from factory between the terminals JP1 and JP2 has to be kept as it is Fo...

Page 16: ...the power contactor 2 with 400V AC coil and NO contact of 5A 1A at least 4 Cable installed from factory as a bridge mode in any TWIN 3 PRO 10 kVA equipment Remove this cable fitted in as a bridge mode...

Page 17: ...connection JP2 Output neutral N Output phase U L Output earth bonding UPS connection power block TWIN PRO UPS connection power block TWIN 3 PRO 10 kVA UPS connection power block TWIN 3 PRO up to 10 k...

Page 18: ...the first bat tery module and from this last negative to the second module and so on Proceed in the same way to connect the red posi tive cable and the green yellow earth cable In parallel systems th...

Page 19: ...and it can t be extended under any other concept due to the risk of interfer ences and communication failures that it could cause In those installations with only one UPS the Jumper cable as bridge mo...

Page 20: ...ion software 5 3 8 2 Smart slot UPS s have a unique slot for TWIN PRO and two slots for TWIN 3 PRO hidden rear the covers stated in the views of the equipment One of them allows inserting the SNMP car...

Page 21: ...h makes a user friendly interface of monitoring and management This software supplies an auto Shutdown for a system based on several PCs in case of an electrical blackout With this soft ware the end u...

Page 22: ...will be done gradually to avoid any problem as minimum in the first commissioning If inductive loads with big inrush current apart from sensi tive ones are required to be connected like laser printers...

Page 23: ...ck that the battery switch is in position On models B0 and B1 Turn the input M1 and bypass M2 circuit breakers to On Switch M2 is only available in models TWIN 3 PRO 10 kVA In equipments with single p...

Page 24: ...sfer to Bypass mode Put all the equipments on manual bypass To do it re move the cover from manual bypass switch which is located at the back of each equipment and turn all the switches to position BY...

Page 25: ...S T S Press over the shutdown key in any UPS for more than 3 seconds and each one will be shutdown supplying output voltage through the bypass Turn On the output circuit breaker switch of the distrib...

Page 26: ...UPS and put the mechanical lock To avoid wrong manoeuvring the mechanical lock has to be fit otherwise the equipment and loads are exposed to serious damages even the de struction of both or fire Turn...

Page 27: ...r 1 sec as minimum to validate the modified option and change the settings Table 6 Functionality of the buttons or keypad of the control panel The UPS has a control panel with the following parts Four...

Page 28: ...s UPS only 8 20 kVA TWIN 3 Blue 81 Fault Heatsink over temperature Red Code Condition Description Color LCD 82 Alarm Ambient over temperature UPS only 4 10 kVA TWIN Blue 83 Alarm Ambient NTC abnormal...

Page 29: ...UPS power supply information single phase input Fig 17 Main screen of the equipment with single phase input Information of load level connected to the UPS UPS power supply information three phase inpu...

Page 30: ...ls due to fault or wrong the equipment will transfer to Battery mode to feed the load s properly Fig 24 Frequency converter mode screen This function can be activated through the settings of the contr...

Page 31: ...beadaptedto the own needs and optimise the function of the equipment 7 3 1 Main screen From main screen when pressing the key or for less than 1 sec it is shown detailed information about the alarm pa...

Page 32: ...UPS status menu Structure of main menu Press 1 sec Fig 31 UPS status screen Press 1 sec Press o 1 sec Structure of Data logger submenu Structure of main menu Press 1 sec Fig 32 Event logger submenu Pr...

Page 33: ...T S password only Fig 34 Control submenu screens 7 3 5 Control submenu When pressing the key the key for less than 1 sec from this Control submenu it is accessed to the control structure see figure 34...

Page 34: ...ation from factory 7 4 1 Operating on ECO mode 7 4 1 1 Short description of the ECO mode ECO mode function allows supplying the load s from mains directly through the internal filters only meanwhile t...

Page 35: ...rs or service cen tres in order to avoid overheating and sparks with fire risk because the size is not enough Do not short the and poles of the batteries there is risk of fire or electrocution Be sure...

Page 36: ...ooling and the ambient temperature of the room NTC abnormal UPS internal fault Consult with the S T S Communication cable male disconnected Para cable Male Loss Alarm code E3 Parallel bus cable is dis...

Page 37: ...er Under Voltage Inv Under Voltage Alarm code 33 UPS internal fault Consult with the S T S Inverter Softstart Failed Inv Softstart Fail Alarm code E34 UPS internal fault Consult with the S T S Negativ...

Page 38: ...ypothetical fault 8 3 2 Out of scope of supply Our company is not forced by the warranty if it appreciates that the defect in the product doesn t exist or it was caused by a wrong use negligence insta...

Page 39: ...oad 2 Voltage THD with non linear load 5 Output voltage recovering time 100 ms IEC 62040 3 70 ms IEC 62040 3 60 ms IEC 62040 3 Transient response of the output voltage with load fluctuation of 0 100 0...

Page 40: ...ending on model 273 V DC 13 65 V DC block 4 A 345 6 V DC 14 4 V DC block Floating voltage block set 13 65 V DC 273 V DC 13 65 V DC 327 6 V DC Maximum charging current 1 A 1 4 A 4 A Recharging time 5 h...

Page 41: ...mitting Diode Circuit breaker A circuit breaker or switch is a device ready to break the electrical current of a circuit when it over comes the maximum set values On Line mode Regarding to an equipmen...

Page 42: ...42 USER MANUAL...

Page 43: ...43 SALICRU...

Page 44: ...mpany salicru salicru_SA Product Range Uninterruptible Power Supplies UPS Lighting Flow Dimmer Stabilisers DC Power Systems Static Inverters Photovoltaic Inverters Voltage stabilisers The Technical Se...

Reviews: