28
SALICRU
9. ANNEXES.
9.1. GENERAL TECHNICAL SPECIFICATIONS.
Models.
ADVANCE RT2.
Available power ratings (VA / W).
800 / 720
1,100 / 990
1,500 / 1,350
2,000 / 1,800
3,000 / 2,700
Technology.
Line-interactive with sine-wave output.
Input.
Input type.
Single-phase.
Number of cables.
3 cables - Phase R (L) + Neutral (N) and earth.
Rated voltage.
208 / 220 / 230 / 240 V AC
(1)
Input voltage range.
176.. 288 V AC
Input frequency range.
45.. 55 / 55.. 65 Hz ± 0.2 Hz; auto-detectable.
Permissible power factor loads.
0.9
Cold start (from batteries).
Yes, by default with frequency of 50 Hz.
Inverter.
Technology.
PWM
Waveform.
Pure sine wave.
Power factor.
0.9
Rated voltage.
208 / 220 / 230 / 240 V AC
(1)
, selectable
Output voltage accuracy (battery mode).
± 1.5 %
Total harmonic distortion (THDv), with linear load.
< 2 %
Frequency.
With mains present, synchronised to rated input (45.. 55 / 55.. 65 Hz).
With mains absent -backup mode- 50 / 60 ±0.1 Hz.
Transfer time, line mode to battery mode (normal
mode).
2..6 ms
Performance at full load, in normal mode with
battery 100% charged.
> 97 %
Performance at full load, in battery mode.
> 89 %
> 90 %
> 91 %
> 92 %
Overload in line mode
103.. 120 %: 5 min
> 120.. 150 %: 10 s
> 150 %: 1 s
Overload in battery mode.
103.. 120 %: 1 min
> 120.. 150 %: 10 s
> 150 %: 0.5 s
Crest factor.
3:1
Batteries (AGM sealed 3 - 5 years life).
Element voltage.
12 V DC
Capacity.
7 Ah
9 Ah
7 Ah
9 Ah
Number of batteries in device connected in series
/ group voltage.
2 / 24 V DC
4 / 48 V DC
6 / 72 V DC
Number of accumulators in battery module
connected in series x no. packs in parallel / group
voltage.
2 x 2 / 24 V DC
4 x 2 / 48 V DC
6 x 2 / 72 V DC
Low battery voltage.
22.4 V DC
44.8 V DC
67.2 V DC
Blocking voltage for group end of backup.
19.2 V DC
38.4 V DC
57.6 V DC
Internal battery charger.
Group floating voltage.
27.2 V DC
54.4 V DC
81.6 V DC
Maximum charge current.
1.5 A
Recharge time.
8 hours to 90%
4 hours to 90%
3 hours to 90%
4 hours to 90%
Optional internal battery charger (B1).
Maximum charge current.
8 A
Other functions.
Cold start.
Yes
Emergency power off (EPO).
Yes
IEC output sockets programmable at disconnection,
for non-critical loads.
Yes
General.
IEC input connectors.
10 A IEC 14 connector.
16 A IEC 20 connector.
IEC output connectors.
8 x 10 A IEC 13 (4 for critical loads + 4 for non-critical loads programmable at disconnection) +
1 x 16 A IEC 19 (only in 3 kVA model)
Communication ports.
2 (1 x RS232 -DB9- and 1 x USB, mutually exclusive).
Potential-free contacts.
Yes, using optocouplers in the same connector as the RS232.
Connectors with protection for ADSL/fax/modem.
RJ45 connectors, 1 input and 1 output.
YOUR CONNECTION TO SAFETY
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• www
.thiele-kg.de
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• www
.thiele-kg.de
YOUR CONNECTION TO SAFETY
klick to
www
u-s-v
YOUR CONNECTION TO SAFETY
klick to
www
ACDC-DCDC
YOUR CONNECTION TO SAFETY
klick to
www
SYSTEME
YOUR CONNECTION TO SAFETY
klick to
www
CONTACT
YOUR CONNECTION TO SAFETY
klick to
www
CALLBACK