35
Parameter 2 setting.
–
Select «Add
»
or «Sub
» to set the battery voltage to
the real figure
.
Parameter 3 setting:
–
The voltage range is from 0 to 9,9 V and the preset
factory figure is 0 V.
•
Code 14
(TWIN PRO2, TWIN/3 PRO2)
.
Charger voltage setting.
Fig. 47.
Parameter 2 setting.
–
It can be selected «Add
»
or «Sub
» to set the charger
voltage
.
Parameter 3 setting:
–
Voltage range is from 0 to 9.9 V and the preset fac-
tory figure is 0 V.
Before doing any voltage setting, check that the bat-
teries are disconnected before setting the charger
voltage.
The setting must be according to the battery specifications.
•
Code 15
(TWIN PRO2)
. Inverter voltage set-
ting.
Fig. 48.
Parameter 2 setting.
–
Select «Add
»
or «Sub
» to set the inverter voltage
.
Parameter 3 setting:
–
The voltage range is from 0 to 9.9 V and the preset
factory figure is 0 V.
•
Code 15
(TWIN/3 PRO2)
. Inverter voltage
setting.
Fig. 49.
Parameter 2 setting.
–
Select «Add
»
or «Sub
» to set the inverter voltage
.
Parameter 3 setting:
–
The voltage range is from 0 to 6 V and the preset
factory figure is 0 V
•
Code 16
(TWIN PRO2, TWIN/3 PRO2)
.
Output voltage setting.
Fig. 50.
Parameter 3 setting:
–
It is displayed the measured internal output voltage
figure. It can be set by pressing the Up or Down keys
according to an external voltmeter. The calibration will
be effective once the Enter key has been pressed. The
calibration range limit is +/-9V. This function is usually
used in parallel systems.
WARNING with regard to codes from 13 to 16!:
DEPENDING ON THE FIRMWARE VERSION OF
THE EQUIPMENT, THE ORIGINAL FACTORY SET-
TINGS CAN BE CHANGED.
DO NOT CHANGE THEM, BECAUSE DEPENDING
ON THE SETTING THE UPS, LOADS OR BOTH
COULD BE DAMAGED.
SLC TWIN PRO2
UNINTERRUPTIBLE POWER SUPPLY (UPS)
USER'S MANUAL