6. MAINTENANCE
6.1. SAFETY INSTRUCTION
Unplug unit from mains before opening the door (disconnect the power plug from the outlet or if there is a two-pole automatic circuit
breaker installed – disconnect it as well. It is necessary to ensure that it won’t be turned on by third parties) and wait until the full stop of
the fans (for about 2 min.).
6.2. GENERAL RECOMMENDATIONS FOR THE MAINTENANCE OF VENTILATION SYSTEM
In order to ensure proper functioning of the system, maintenance requirements and its periods should be followed. Otherwise the warranty shall
not be valid. Some recommendations are provided in the table below, but they are just advisory, as the need of system maintenance depends on
the place of the device installation, the pollution of the atmosphere, the population, the working hours and etc.
COMPONENT
DURING START-UP
AT LEAST EVERY 6 MONTHS
Filters
Check the cleanliness of the filters
Replace filters every 3 to 4 months or according to the control
device indications.
Fans
Check the connections and the
direction of rotation
Check cleanliness. Clean, if necessary
Make sure that the impellers are not unbalanced.
Make sure that the impellers do not cause noise when rotated by
hand.
Make sure that the fastening screws are not loose and free of
mechanical damage.
Check electrical connections and make sure that these are se-
cured properly and are free of signs of corrosion.
Plate Heat exchanger
Check the cleanliness of the heat
exchanger
Check cleanliness and clean, if necessary
Control panel
Check the connections
Check the connections
Electric heater
Check the connections
Clean off dust, and check the electrical components and connec
-
tions of the heater
Presure senssor
Check electrical connections
Check the operation
Temperature senssor
Check electrical connections
Check the operation and tune up, if necessary
Air intake and discharge system
Check the connections
Clean
Air duct system
Check the tightness
Clean
Dampers, diffusers, grid
Check the tightness of connections Clean
Switching unit (contactor)
Every 3 to 4 months, visually assess the functioning of the switch-
ing unit (contactor), i.e. make sure that its casing has no signs
of melting or is not thermally damaged otherwise and does not
produce any unusual sounds. All the contactors in the product or
in its accessories must be checked.
Condensate trap and discharge
assembly
Check the condensate discharge
assembly and make sure that wa-
ter runs from the bath properly.
Clean
6.3. COVER OPENING
Figure 6.3.1. Smarty 2XV
Figure 6.3.2. Smarty 3XV/4XV
Summary of Contents for SMARTY XV Series
Page 1: ...SMARTY XV EN MOUNTING AND INSTALLATION INSTRUCTION...
Page 23: ...EN 23 SMARTY XV v2020 2 EKA NIS connection...
Page 30: ...30 EN SMARTY XV v2020 2 Figure 8 1 9 2 Smarty 2XV 1 1 Smarty 2XV 3XV 4XV 1 2 219 1017 0 1 2 PS...
Page 49: ...49 SMARTY XV v2020 2...
Page 50: ...50 SMARTY XV v2020 2...
Page 51: ...51 SMARTY XV v2020 2...