Unplug unit from mains before opening the door (disconnect the power plug from the outlet or if there is a two-pole automatic circuit
breaker installed – disconnect it as well. It is necessary to ensure that it won’t be turned on by third parties) and wait until the full stop of
the fans (for about 2 min.).
Dirt increases air resistance in the filter, therefore less air is sup-
plied into the premises.
It is recommended to change the filters every 3-4
months, or in accordance to filter timer.
Proceed to maintenance and repair after any rotation in the fan stopped.
Clean the heat exchanger once a year.
Firstly take out heat exchanger cassette carefully. Submerge it into a bath and wash with warm soapy water (do not use soda). Then rinse it with
weak hot water stream (too strong stream can fold the plates). Place back the heat exchanger only when it is completely dry.
Reset the filter timer in control panel after change of the
filters.
There is no need to remove the cover.
Taking off the filters:
• Open filter cover (pulling the strap).
• Remove the filter.
• Use filters of G4 class/(or F7 as an option).
Do not connect the elbows in vicinity of the connection
flanges of the unit. The minimum distance of the straight
air duct between the unit and the first branch of the air
duct in the suction air duct should be 1xD, in air exhaust
duct 3xD, where D is diameter of the air duct.