background image

46

Smarty 2R VE / 2R VE plus

www.salda.lt

• Electrical connection can only be implemented by the qualified electrician in accordance with the applicable international and national electrical 

safety requirements and requirements for installation of electrical devices.

• Use only power source which meets the requirements specified on the device label.

• Power supply cable should be selected based on the electrical specification of the device. If the device power supply line is far from the unit, the 

distance and voltage drop should be considered.

• Device must be earthed.

• Install the control panel at the designated place.

• Install the supplied connection cablebetween the control panel and the HVAC unit. It is recommended to install the control panel separately from 

the power cables.

NOTE

: If cable is used together with other power cables, shielded control panel cable with earthed shield should be used.

NOTE: 

The remote control panel can be connected and (or) disconnected only after disconnecting the power supply for the HVAC unit.

• Select the desired fan rotation speed and the supply air temperature using the remote controller.

Control system of the unit has an integrated protection against short-circuit for these functional components. The controllers have the following protec-

tions:

MCB

F1, F2 - 1A(5x20) MCB protection

Prior to start-up the system must be thoroughly cleaned. Check whether:

• operation systems and unit elements as well as automation and automation devices were not damaged during installation,

• all consumers are connected to power supply and fit for service,

• all necessary automation elements are installed and connected to power supply and MCB terminal blocks,

• cable connection to MCB terminal blocks comply with the existing power connection diagrams,

• all electrical equipment protection elements are properly connected (if they are additionally used),

• cables and wires correspond to all applicable safety and functional requirements, diameters, etc.,

• earthing and protection systems are properly installed,

• condition of all seals and sealing surfaces is proper.

To ensure safe maintenance of the unit, it is necessary 

to remove the plug from the power network.

Failure

Cause

Explanation / corrective actions

Unit is not operating

No supply voltages

Check whether the device is connected to the 

plug socket

Two-pole  protection  device  is  off  or  a  current 

leakage  relay  is  active  (if  installed  by  the  in-

staller)

Switch  on  only  if  the  unit  condition  has  been 

evaluated by a qualified electrician. If the sys-

tem failed, the failure MUST BE rectified prior 

to switching it on.

Air supply heater or heater is not operating or 

malfunctioning (if installed)

Too low air flow in air ducts activates automatic 

protection 

Check if air filters are not clogged

Check if fans are rotating

Manual protection is activated

Possible heater or unit failure. MUST address 

the  servicing  staff  for  failure  detection  and  its 

elimination.

Too low air flow at rated fan speed 

Clogged supply and/or extract air filter(s)

Filter replacement needed

Filters are clogged and no message is shown 

on the remote control

Wrong time in filter timers

Shorten  filter  timer  time  till  the  message  of 

clogged filters

The controller is used with NTC sensors.

Default sensor NTC

10 kΩ β (25/85) 3977

Limits for temperature measurement -30 ...105 °C.

Accuracy - ± 0,2 %

Safety class – IP-54

For the ventilation unit to work properly, perform the inspection of the entire ventilation system once a year. Check if the air inlet grating and room air

supply devices are clean. Check if the air duct system is not dirty. If necessary, clean or replace these devices.

Summary of Contents for Smarty 2R VE

Page 1: ...Subject to technical modification Smarty 2R VE_P0108_AZ_0003 AHU WITH HEAT RECOVERY Smarty 2R VE Smarty 2R VE plus User and service technical manual...

Page 2: ...ime 26 The principal connection scheme of internal and external components control Smarty 2RVER MCB 0 3k 27 The principal connection scheme of internal and external components control Smarty 2RVER MCB...

Page 3: ...ble place or on the dashed place of a technical manual in order to keep the important information about the unit STICK HERE 200003025238 IV PV KE PE M 0 084 kW 0 92 A 230 50 V Hz 1 0 085 kW 0 93 A 230...

Page 4: ...g Do not wear loose clothing that could be entangled in to operating unit If a outside object enters the unit immediately disconnect power source Before removing object make sure that any mechanical m...

Page 5: ...1 Power supply cable collar 2 Extract air filter 3 Exhaust air fan 4 Extract air temperature sensor 5 Control box 6 Rotor 7 Rotor belt 8 Spare rotor belt 9 Kitchen hood hole 10 Mounting brackets 11 F...

Page 6: ...3 4 months or in accordance to filter timer Smarty 2R VE Smarty 2R VE plus Dirt increases air resistance in the filter therefore less air is supplied into the premises Taking off the filters Open cove...

Page 7: ...erated wear on motor bearings and noise vibration Clean impeller and inner housing with mild detergent water and damp soft cloth Do not use high pressure cleaner abrasives sharp instruments or caustic...

Page 8: ...ctivation of the manually restored protection the unit must be disconnected from the power supply Wait until the heating elements cool down and the fans stop rotating After identifying and removing th...

Page 9: ...or heat exchanger can be easily removed from the unit The power cord of the motor of the heat exchanger is disconnected The clamp of rotor heat exchanger section is released and raised and the heat ex...

Page 10: ...1xD in air exhaust duct 3xD where D is diameter of the air duct It is recommended to use the accessories holders This will reduce vibration transmitted by the unit to the air duct system and environm...

Page 11: ...ve the middle part of the insulating ring Cut the connecting opening as indicated on the insulation material Carefully remove the lid which covers the electric connection for the connection of the ele...

Page 12: ...wires cables and power network plug socket distribution devices Prior to carrying out any ventilation unit installation and connection activities until its hand over to the customer the unit must be...

Page 13: ...IP44 IP54 control imput VDC 0 10 0 10 Total power current kW A 0 75 3 91 0 77 4 13 Automatic control integrated Insulation of walls mm 20 20 Weight kg 36 36 Exhaust air filter class class M5 M5 width...

Page 14: ...00 250 65 70 75 80 100 100 80 80 70 70 60 60 50 50 40 100 100 80 80 70 70 60 60 50 50 40 50 50 Specific fan power SFP Specific fan power SFP 800 700 600 500 400 300 200 100 0 100 200 300 28 56 83 111...

Page 15: ...TL Outdoor air temperature sensor Stouch Control panel TA Extract air temperature sensor Ptouch Control panel EKA NV PH Outdoor air electric preheater Lower than 20 o C use preheater Cooker hood Kitch...

Page 16: ...CO2 sensor S RCO2 F2 ZAKKT0048 CO2 sensor S KCO2 ZAKKT0049 Cooker hood for stainless steel Cooker hood ZPGKT0042 Cooker hood for white Cooker hood ZPGKT0041 Front coover mounting bracket Mounting bra...

Page 17: ...PUVRA009 Smarty 2R VE Fan supply exhaust Fan GVESMARTY001 Smarty 2R VE plus Rotor box Rotor box GPURSD085_330 Temperature sensor 3 m TJ PJUT0063 Temperature sensor 1 5 m TL TA PJUT0062 Controler MCB V...

Page 18: ...ction Weekly holiday schedule User and service control levels Manual air flow balancing CO2 level indication and reduction function Night cooling function Relative humidity RH level indication and red...

Page 19: ...by mode blocking function settings The building protection mode is designed to protect a building against moisture accumulation In this mode the system operates at speed 1 By default in this mode temp...

Page 20: ...ts and user interface Weekly Schedule Mode external switch Holiday Schedule Stand by mode blocking Protection against Dryness Boost ventilation Ventilation logics Protections Ventilation logics blocki...

Page 21: ...ding protection 2 Economy 3 Comfort 4 BOOST function Fan speed can be controlled based on Percentage value Speed percentage is indicated 0 corresponds to 0V control signal voltage 100 corresponds to 1...

Page 22: ...checked 1 Time does not correspond to the start end interval 2 Extract air temperature drops below the set point 3 Outdoor air temperature drops below the set point 4 Mode other than Comfort was switc...

Page 23: ...ntage for activating the rotor is indicated in the window SERVICE HEAT EXCHANGER If bypass damper opens just some percent noise may occur so minimal opening of the damper is limited and this limit is...

Page 24: ...rds can be changed in the service environment To change passwords of service and adjuster environments the password must be activated The password consists of 4 digits If password is not necessary for...

Page 25: ...IR TEMPERATURE SENSOR FAILURE SYSTEM STOPPED A14 HYDRAULIC HEATER WATER TEMPERATURE SENSOR FAILURE SYSTEM STOPPED A15 HYDRAULIC PREHEATER WATER TEMPERATURE SENSOR FAILURE SYSTEM STOPPED A16 HYDRAULIC...

Page 26: ...tem configuration and software ver sions the running time is also displayed since the unit manufacture date Running time is calculated when fans are rotating W12 HYDRAULIC PREHEATER WATER TEMPERATURE...

Page 27: ...63 64 61 15 127 127 58 57 12 124 125 126 46 126 28 51 121 122 123 103 28 51 121 124 46 61 15 2 01 2 2 01 2 2 01 2 2 01 2 2 01 2 2 01 2 F1 1A 1 2 2 01 2 65 65 58 12 2 01 2 2 01 2 R2 03 7 3 11 14 C1 1...

Page 28: ...D X14 4 AO2 0 10VDC RG1 MCB V1 0 Extract fan speed RPM Extract air fan 0 10V control Supply air fan 0 10V control X2 1 PE X2 2 GND X2 3 24VDC X2 4 HOLO IN RG1 MCB V1 0 Rotor RPM X3 1 DI1 X3 2 12VDC X3...

Page 29: ...4 R2 19 Heater power supply DX cooler Rotor motor power supply Punktyrine linija pa ym tus komponentus ir kabelius pajungia SALDA arba vartotojas Components and cables marked with the dash line connec...

Page 30: ...L RG1 MCB V1 0 X5 1 AI1 NTC X5 2 GND X5 3 AI2 NTC X5 4 GND X5 5 AI3 NTC X5 6 GND X5 7 AI4 0 10VDC X5 8 GND RG1 MCB V1 0 0 10V GND 24VAC DC Transmitter1 33 32 Punktyrine linija pa ym tus komponentus ir...

Page 31: ...15 PE N L1 GND 10V 0 10Vin TACH GND TACH 10V L1 N PE 0 10Vin 21 25 10V GND 10V GND PV RPM IV RPM 22 23 26 27 23 22 27 26 GND 0 10V GND 0 10V IV control PV control 1 01 3 1 01 3 1 01 3 1 01 3 1 01 3 1...

Page 32: ...Fresh air temperature sensor X29 890 203 L PE N Electric heater 103 125 73 1 01 5 1 01 5 1 01 5 X21 L PE N Cooker hood power supply 122 122 57 57 64 64 1 01 4 115 114 73 103 125 116 116 W4 white 117...

Page 33: ...asiliauskas Pyn l RSD SMARTY2 S1 R 3k 5 0013 0 1 0 PS 3k Connections principal scheme 4 01 2016 06 07 2016 06 07 T K Grik as 2016 06 07 Rotor morot HALL sensor PE COM S1 C L1 N 24V DC 40 39 38 X40 890...

Page 34: ...Drawing Book APPROVED BY 1 2 3 4 5 6 7 8 9 10 EI O Dr sutis EI D Aleksandravi ius Pyn l S1 0 2m 2k 5 0014 0 1 0 PS 2k Connections principal scheme 5 01 2016 06 06 2016 06 06 K Grik as 2016 06 06 24V...

Page 35: ...H GND 0 10Vin 0 10Vin 1 2 3 4 5 6 X32 7 8 794821 1 1 2 3 4 5 6 X33 7 8 794821 1 PE N L 10V TACHO GND 0 10V PV R3G140 AW05 12 100 W1 PE PE N L 10V TACHO GND 0 10V IV R3G140 AW05 12 107 W2 PE 101 W1 N 1...

Page 36: ...7 8 9 10 EI O Dr sutis EI D Aleksandravi ius ildyt SRR 0 6 1f EC 0k 1 680 200 5 0 PS 1k Principle scheme 7 01 2016 06 07 2016 06 07 2016 06 07 X29 890 713 L PE N 70 70 55 55 69 69 EK1 AT1 RT1 60 60 56...

Page 37: ...37 Smarty 2R VE 2R VE plus www salda lt A C B A B C...

Page 38: ...VDC X4 1 MCB DI4 Fire protection input NC 2 12VDC 3 MCB DI5 External switch 4 12VDC 5 MCB DI6 Pressure compensation if overcooked 6 12VDC 7 MCB DI7 Not used 8 12VDC X5 1 MCB AI1 NTC Supply air tempera...

Page 39: ...ND 3 MCB BYPASS_ 24VDC_OPEN El heater relay 4 MCB BYPASS_ 24VDC_CLOSE Rotor motor relay X12 1 PE Not used 2 GND 3 24VDC X13 1 24VDC Not used 2 STEP_B 3 STEP_B 4 STEP_A 5 STEP_A 6 24VDC X14 1 GND Suppl...

Page 40: ...oom RH converter S RFF U D F2 1 Set that next to 0 10 V input an extracted air RH converter is connected Service Sensors 0 10 VDC sensors Air quality sensor 2 choose Extract RH 2 Indicate Air quality...

Page 41: ...t air duct Tool for drilling holes are required for its installation CO 2 concentration ppm 3000 Effect on an individual 2500 2000 Reduced concentration drowsi ness headache etc 1500 1000 Pettenkofer...

Page 42: ...ted In factory the short circuiter is applied KEFA KF2EDGKD 2 5 8P X4 connector 1 and 2 contacts Fire protection signal MCB X4 1 2 Functions are activated using external switches Pressure compensation...

Page 43: ...22_A RS422_B GND signal 24VDC GND power ModBus RTU ModBus RTU ModBus RTU TCP IP ModBus RTU or or The app MCB tool is for importing control board MCB settings from MCB to the media in a computer and to...

Page 44: ...IP Modbus gateway MB GATEWAY B5 Press to connect B4 B5 2 Connect to device press CONNECT button I2 Device software version I3 Configuration read status I4 Configuration write status B6 Press to discon...

Page 45: ...Read configuration from device and save to your computer press READ CONFIG FROM BOARD button and write configuration file name 4 Write configuration to device from your computer press WRITE CONFIG TO...

Page 46: ...erminal blocks comply with the existing power connection diagrams all electrical equipment protection elements are properly connected if they are additionally used cables and wires correspond to all a...

Page 47: ...1 mechanical damage 4 2 damage caused by entering outside objects materials liquids 4 3 damage caused by natural disaster accident voltage change in the electricity network lightning etc 5 The compan...

Page 48: ...nstalation Fan cleaning Once a year Heat exchanger cleaning Once a year Filter replacement Every 3 4 months NOTE The purchaser is required to fill in the Product maintenance table 2 At least 2 Look at...

Reviews: