8
| EN
RIS 1200-2500 P EKO 3.0 v2020.1
RIS EKO 3.0
2500 PE 4.5
2500 PE 9.0
2500 PE 18.0
2500 PW
Exhaust air fan
phase/voltage
[50 Hz/VAC]
~1, 230
~1, 230
~1, 230
~1, 230
SRZHUFXUUHQW
[kW/A]
0,72/3,1
0,72/3,1
0,72/3,1
0,72/3,1
speed
[min
-1
]
2800
2800
2800
2800
control input
[VDC]
0-10
0-10
0-10
0-10
protection class
IP-54
IP-54
IP-54
IP-54
Supply air fan
phase/voltage
[50 Hz/VAC]
~1, 230
~1, 230
~1, 230
~1, 230
SRZHUFXUUHQW
[kW/A]
0,72/3,1
0,72/3,1
0,72/3,1
0,72/3,1
speed
[min
-1
]
2800
2800
2800
2800
control input
[VDC]
0-10
0-10
0-10
0-10
protection class
IP-54
IP-54
IP-54
IP-54
Integrated electrical heater
[kW]
4,5
9,0
18,0
-
7RWDOSRZHUFXUUHQWFRQVXPSWLRQ
[kW/A]
5,93/12,7
10,43/19,2
19,43/32,2
1,43/6,2
Automatic control integrated
PRV
PRV
PRV
PRV
,QVXODWLRQRIZDOOV
[mm]
50
50
50
50
([KDXVWDLU¿OWHUFODVVGLPHQVLRQV/[:[+
[mm]
MPL 972x438x46
ePM10-55
MPL 972x438x46
ePM10-55
MPL 972x438x46
ePM10-55
MPL 972x438x46
ePM10-55
6XSSO\DLU¿OWHUFODVVGLPHQVLRQV/[:[+
[mm]
MPL 972x438x46
ePM1-70
MPL 972x438x46
ePM1-70
MPL 972x438x46
ePM1-70
MPL 972x438x46
ePM1-70
Device protection class
IP-34
IP-34
IP-34
IP-34
$FRXVWLFGDWDFKHFNWKHSURGXFWSDJHRQZZZVDOGDOW
Not suitable for installation in living rooms: additional noise insulation required.
4.4. OPERATING
CONDITIONS
RIS EKO 3.0
1200 PE/PW
1900 PE/PW
2500 PE/PW
Minimum outdoor air temperature
-2
o
C
-2
o
C
-2
o
C
Maximum outdoor air temperature
+40
o
C
+40
o
C
+40
o
C
Minimum extracted air temperature
+15
o
C
+15
o
C
+15
o
C
Maximum extracted air temperature
+40
o
C
+40
o
C
+40
o
C
Maximum extracted air relative humidity
Minimum ambient air temperature
+5
o
C
+5
o
C
+5
o
C
Maximum ambient air temperature
+40
o
C
+40
o
C
+40
o
C
Installation
Indoor
Indoor
Indoor
4.5. STANDARD PACKAGE OF COMPONENTS
RIS EKO 3.0
1200 PE/PW
1900 PE/PW
2500 PE/PW
Anti-vibration rubber 313508000
8
8
8
Key 291103
1
1
1
Hose 16x20 Cristal transparent
300 mm
-
-
&ODPSZLWKKDQGOH
1
-
-
Suspension bracket
-
8
8
Bolt 5 R DIN440
-
16
16
6SULQJZDFKHU',1
-
16
16
Washer 5x20 DIN7985
-
16
16