Salda RIRS 400 V EKO 3.0 Series Mounting And Installation Instructions Manual Download Page 10

10 

| EN

RIRS 400-700 V EKO 3.0 v2019.06

18.2.  FAN

- Maintenance and repair should only be performed by experienced and trained staff.

- The fan should be inspected and cleaned if needed at least once a year.

- Be sure the fan is disconnected from power source before performing any maintenance or repair.

- Proceed to maintenance and repair after any rotation in the fan stopped.

- Observe staff safety regulations during maintenance and repair.

- The motor is of heavy duty ball bearing construction. The motor is completely sealed and requires no lubrication for the life of the motor.

- Detach fan from the unit (1-2-3).

- Impeller should be specially checked for buil-up material or dirt which may cause an imbalance.  Excessive imbalance can lead to accelerated 

wear on motor bearings and vibration.

- Clean impeller and inside housing with mild detergent, water and damp, soft cloth.

- Do not use high pressure cleaner, abrasives, sharp instruments or caustic solvents that may scratch or damage housing and impeller.

- Do not plunge impeller into any fluid.

- Make sure, that impeller’s balance weights are not moved.

- Make sure the impeller is not hindered.

- Mount the fan back into the unit. Replace fan guards and connect the fan to power supply source (3-2-1).

- If after maintenance or repair the fan does not start either thermal protection contact activates automatically, contact the manufacturer.

- During the maintenance do not hold the fan by the impeller, it might cause disbalance of impeller or damage it. Hold the fan by the casing.

18.3.  HEAT EXCHANGER

Be sure the unit is disconnected from power source before performing any maintenance or repair.

Proceed to maintenance and repair after any rotation in the fan stopped.

Clean it once a year.

The maintenance works for the rotor heat exchanger shall be carried out once a year.

Ensure that the gaps of the heat exchanger are not contaminated, the seal brushes are not worn, the belt drive is not worn and the clamp assem-

blies are tight.

The rotor heat exchanger can be easily removed from the unit by disconnecting the power supply cable of the heat exchanger motor (Pic. 1-2).

The heat exchanger is cleaned using the solution of warm water and non-corrosive toward aluminum alkaline agent or the air stream. It is not 

recommended to apply direct stream of liquid as it can harm the heat exchanger.

It is 

NECESSARY

 to protect the motor of the heat exchanger from the moisture and liquid while cleaning the heat exchanger.

CAUTION!

 It is forbidden to use the heat exchanger if the fi lters are removed!

18.4.  ELECTRICAL HEATER

Electrical heater does not need to be serviced additionally. It is compulsory to change filters as described above.

Heaters have 2 thermal protections: automatically self-resetting, which activates at +50°C and the manually restored, which activates at +100°C.

After the activation of the manually restored protection, the unit must be disconnected from the power supaply. Wait until the heating elements cool 

down and the fans stop rotating. After identifying and removing the reason of failure, to start the unit, press the “

reset

” button. 

The failure can be 

identified only by a qualified professional.

It’s possible to take out electrical heater, if there is a need. Unplug the X6 connector from the automation box and pull the heater together with the 

attached wiring harnesses.

Summary of Contents for RIRS 400 V EKO 3.0 Series

Page 1: ...RIRS 400 700 V EKO 3 0 EN MOUNTING AND INSTALLATION INSTRUCTION...

Page 2: ...R 9 17 2 POSSIBLE FAULTS AND TROUBLESHOOTING 9 18 MAINTENANCE 9 18 1 FILTERS 9 18 2 FAN 10 18 3 HEAT EXCHANGER 10 18 4 ELECTRICAL HEATER 10 19 AUTOMATIC CONTROL 11 19 1 SYSTEM PROTECTION 12 19 2 USING...

Page 3: ...uency Max current Max power consumption Protection class Weight xxx xx VAC Hz x xx A x xx kW IP xx xx kg Made in iauliai Lithuania AHU000000 BN xxxxxx 2019 01 01 SERIAL 2514523357 XXX GAMINIO PAVADINI...

Page 4: ...make sure that it is not stuck or blocked check the grounding make sure that all components and accessories are connected in accordance with the project or provided instructions Danger Fumes Salda An...

Page 5: ...phase voltage 50 Hz VAC 1 1 AVS 250 AVS 250 power consumption kW 2 0 2 0 Fans phase voltage 50 Hz VAC 1 1 1 1 exhaust power current kW A 0 222 1 8 0 222 1 8 0 217 1 88 0 217 1 88 speed min 1 3380 3380...

Page 6: ...15 C o 40 C o 5 C o 40 C o 15 C 10 o o C 40 C o 15 C o 40 C o 3 C o 40 C o 8 PACKAGE H L W RIRS V EKO 3 0 H W L QUANTITY ON THE PALLET mm mm mm units 400 1055 785 1270 1 700 1210 795 1240 1 9 TRANSPOR...

Page 7: ...re delivered before starting the installation Any deviation from the ordered equipment must be reported to the supplier of products 11 STANDART PACKAGE OF COMPONENTS RIRS EKO 3 0 400 VER 400 VEL 400 V...

Page 8: ...re sensor IV Exhaust fan TE Exhaust air temperature sensor KE1 Electric heater DTJ Extract air temperature and RH sensor PE1 Electric pre heater T2 Cooler changeover thermostat KV2 Water pre heater TV...

Page 9: ...nts as well as automation and automation devices were not damaged during installation all electrical devices are connected to power supply and fit for service all necessary automation elements are ins...

Page 10: ...d from power source before performing any maintenance or repair Proceed to maintenance and repair after any rotation in the fan stopped Clean it once a year The maintenance works for the rotor heat ex...

Page 11: ...ped using the START STOP feature STOP is displayed at the remote control panel FLEX In START mode the recuperator operates based on the latest settings of the panel FanFail and FanRun features It prov...

Page 12: ...e cover of the heater When manual thermal protection is triggered fans operate in maximum capacity until the manual heater protection is reset by pressing the reset button and the device is restarted...

Page 13: ...ead_Coils 10 1 Return water temperature sensor alarm 1 a c t i v e o passive 11 ToutDoor 01h_Read_Coils 11 1 Outside air temperature sensor alarm controller continues to work in determining ToutDoor 0...

Page 14: ...ct air damper actuator damper actuator Fire alarm input Air quality transmitter Air quality transmitter Fire alarm input damper actuator damper actuator Extract air Supply air L L control N L control...

Page 15: ...necessary to properly install antifreeze protection from possible freezing of heat carrier Antifreeze temperature sensor TV must be mounted in clamp on return pipe of the water heater Capillary senso...

Page 16: ...9 06 20 1 LABELING CHARACTERISTICS OF THE CONTROLLER AND THE SYSTEM COMPONENTS Contact No Labeling Description I O type Max load Min load A mA X10 L 230V 50Hz power supply I X8 N 230V 50Hz power suppl...

Page 17: ...O X33 5 VAL Cooling valve common Pulse 24v 50hz AO M1 By pass actuator X33 6 DMP Bypass damper opening PWM 24v 50hz AO 100mA X33 7 DMP By Pass damper closing PWM 24v 50hz AO 100mA X33 8 DMP By Pass da...

Page 18: ...2 COM PV Supply air fan X37 1 V1 Supply air fan 0 10V AO X37 2 COM COM IV Extract room s air fan X37 3 V2 Extract air fan 0 10V AO X37 4 COM COM 20 2 REGULAR SYSTEM CHECK UP The operation of the swit...

Page 19: ...16 3 7 8 R1 A1 A2 START NC STOP NO BOOST X33 10 COM X33 9 CHIL X33 2 MIDL X33 1 COM X32 3 TIMER X32 2 HIGH X32 4 COM X32 1 LOW TL X37 L ON OFF ON OFF 230V AC 230V AC L supply 20 L L N N L 18 17 19 M3...

Page 20: ...25 26 27 X38 1 X38 2 X40 3 X40 2 X40 1 TA HR 24V DC C S1 COM 1 X21 2 3 9 8 W3 W2 W1 7 BN BU BK 6 5 N X24 4 3 2 C L N PE R 1 X40 L X31 X33 15 X33 16 COM A 0 10 24VDC 24VDC X41 1 X41 2 X39 2 X39 1 X34...

Page 21: ...EN 21 RIRS 400 700 V EKO 3 0 v2019 06 21 3 RIRS 700 VE EKO 3 0...

Page 22: ...26 27 28 X38 1 X38 2 X40 3 X40 2 X40 1 TA HR 24V DC C S1 COM 1 X21 2 3 9 8 W3 W2 W1 7 BN BU BK 6 5 N X24 4 3 2 C L N PE R 1 X40 L X31 X33 15 X33 16 COM A 0 10 24VDC 24VDC X41 1 X41 2 X39 2 X39 1 X34...

Page 23: ...erage kWh a 4224 4224 4224 4224 AHS Cold kWh a 8262 8262 8262 8262 AHS Warm kWh a 1910 1910 1910 1910 ErP Compliance 2018 2018 2018 2018 Internet address for disassembly instructions www salda lt RIRS...

Page 24: ...24 EN RIRS 400 700 V EKO 3 0 v2019 06 AHS Warm kWh a 1885 1885 1885 1885 ErP Compliance 2018 2018 2018 2018 Internet address for disassembly instructions www salda lt...

Page 25: ...k reduction LST EN 60204 1 2006 Safety of machinery Electrical equipment of machines Part 1 General requirements LST EN 60335 1 2012 Household and similar electrical appliances Safety Part 1 General r...

Page 26: ...ver the equipment to manufacturer Delivery costs should be covered by customer Manufacturer reserves the right to change this technical passport any time without prior notice if some typographic error...

Page 27: ...27 RIRS 400 700 V EKO 3 0 v2019 06...

Page 28: ...NANCE TABLE Product name LOT number Instalation Interval Datum Fan cleaning Once a year Heat exchanger cleaning Once a year Filter replacement Every 3 4 months Look at the product label At least NOTE...

Reviews: