KF T120 EC

Problam

Possible causes

Corrective measures

Fan doesn’t operate smoothly

Impeller’s imbalance

Rebalance ant the specialized company

Adhesions on the impeller

Clean carefully, rebalance, if necessary

Material decomposition on the impeller due to aggres-

sive material conveyed

Contact the manufacturer or its representative

Wrong direction of rotation of impeller

Contact the manufacturer or its representative

Deformation of impeller due to excessive temperature

Contact  the  manufacturer  or  its  representative.  Install 

new impeller. Check mounting

Air output of the fan is too low

Excessive pressure losses in the ducting

Change the ducting routing

Airflow regulators are not or only partly opened

Check the opening position

Intake or exhaust air ducts are blocked

Remove the blocking

Grinding sounds when starting 

or operating the fan

Intake line is strained

Loosen intake line and realign

Thermal  contacts  or  resistors 

have triggered 

Motor blocked

Contact the manufacturer or its representative

Fan can’t reach nominal speed

Regulating devices are not adjusted properly

Check if control device is adjusted correctly

Defective motor winding

Contact the manufacturer or its representative

Motor does not rotate

Mechanical blockage

Switch  off  the  fan,  disconnect  from  the  power  supply 

and remove the blockage

Incorrect supply voltage 

Check the supply voltage, resume the voltage supply, 

and start the fan

Incorrect electrical connection

Disconnect from the power supply, correct the electrical 

connection according presented connection scheme

Temperature indicator has responded

Allow  the  motor  to  cool  down,  find  and  eliminate  the 

cause, release reactivation lock if applicable

Electronics or motor have 

overheated

Insufficient cooling

Improve cooling. Let fan to cool down. In order to reset 

the fault, turn off the supply voltage at least for 25 sec 

and turn on again

Ambient temperature to high

Lower ambient temperature

Impermissible operating point

Change the operating point. Let device to cool down

Summary of Contents for KF T120 EC Series

Page 1: ...Subject to technical modification KF T120 EC_P0109_AZ_0002 KF T120 EC KITCHEN FANS INSTALLATION AND OPERATION MANUAL...

Page 2: ...ckage of components 7 Components 7 Accessories 8 Spare parts 9 Installation 10 Transportation ant storage 10 Unpacking 10 Space requirements 12 Maintenance 12 Electrical connection and control 13 Star...

Page 3: ...nt of failure it must be reported to he manufacturer or its representative with the description of the failure and provide data on product label In the event of a failure it is prohibited to repair di...

Page 4: ...Please note the maximum allowed ambient temperature please see technical data table in page 5 The maximum temperature of transported air can not exceed 120 O C A mm A1 mm B mm C mm C1 mm D mm D1 mm F1...

Page 5: ...0 Hz 1 kHz 2 kHz 4 kHz 8 kHz Supply 84 75 76 82 75 71 67 61 Exhaust 85 76 79 82 76 70 69 64 Surrounding 71 62 64 68 59 54 51 47 Measured at flow pressure m3 h Pa 2603 103 KF T120 F 250 EC LWA all dB A...

Page 6: ...50 40 30 100 90 80 70 60 50 40 30 100 250 400 500 0 5 0 3 0 2 0 1 0 P kW 0 4 100 90 80 70 60 50 40 30 100 70 60 50 40 30 100 KF T120 F 280 EC KF T120 B 315 EC 0 7 0 6 0 5 0 4 0 3 0 2 0 1 0 700 600 500...

Page 7: ...30 4 pcs 3 Screws 8 DIN 934 4 pcs 4 Washers 8 DIN 127 4 pcs 1 The upper flange 2 Hinges 3 Housing 4 Anti vibration feet 5 Connection Ring 6 Fan 7 Fat chutes with a plug 1 2 8 Switch 9 Roof 10 Engine 1...

Page 8: ...itch 25A 3f only KF T120 F280 EC GPU235_1007E Manual regulation MTP010 PRGR0025 SPS differential pressure trans mitter S 1141 ZAKKT0047 Flexible connection for high temperature RC MAN PU 315 ZPDLJ003...

Page 9: ...ox Door 1017 KF 160 GPUD232_1017_1017 Door 1021 KF 180 GPUD232_1021_1021 Door 1023 KF 200 GPUD232_1023_1023 Door 1018 KF 250 GPUD232_1018_1023 Door 1020 KF 280 GPUD232_1020_1020 Door 1019 KF 315 GPUD2...

Page 10: ...its must be transported to the storage or installation site using forklifts The storage is not recommended for a period longer than one year In case of storage longer than one year before the installa...

Page 11: ...LU NPU RC MAN PU CEE7 7 SKG A RSK KF T120 EC Exhaust air Kitchen hood AB AGO ALU Mount air outlet or protective ventilation grill SKG A RSK Mount a damper SKG A or a back draft damper RSK NPU Coupling...

Page 12: ...fan cleaning do not use mechanical cleaners compressed air or water stream aggressive chemicals When cleaning the fan do not deform the impeller avoid moisture or water contact with electrical device...

Page 13: ...tions need to prevent water entering into the connection box Use cables that comply with the currents the stickers Power Switch dry conditions X1 Pic 1 Electrical connection box The fan has to be conn...

Page 14: ...e 1 Green yellow 1 KF T120 F 200 EC KF T120 F 250 EC KF T120 B 400 EC SP26 b KF T120 F280 EC SP27 b W1 green yellow W1 blue W1 brown SP26 b W1 white1 W1 white2 W2 yellow W2 blue W2 red 1 PE X1 2 1 N 2...

Page 15: ...matyt si pajungimo gnybt numeracija lectrical Us max 12VDC 1mA out GND MTP010 max 4A 250VAC 10A 12VDC K2 A1 A2 0 10V GND COM 1 4 2 1 3 2 1 2 2 1 5 2 10V L1 L3 L2 1 L2 2 1 L1 2 1 L3 2 NC 1 1 2 PE L2 L1...

Page 16: ...9 1 4 2 1 3 2 1 1 2 1 L1 2 1 N 2 1 PE 2 1 2 2 GND 10V Tacho L1 N PE 0 10V PE L1 N F7 1 2 F8 1 2 PE Q3 1 2 3 4 5 6 Stouch 1 24VDC AC 2 24VAC DC 3 GND 4 RS465 B 5 RS485 A 6 GND 7 0 10VDC IN 8 0 10VDC OU...

Page 17: ...y a remote controller or and a PC via Modbus see Stouch manual CEE7 7 ModBus CEE7 7 SPS CEE7 7 ModBus 3 Constant pressure adjustment by a remote controller or and a PC via Modbus see Stouch manual CEE...

Page 18: ...4 10V GND 1 3 2 1 4 2 0 10V N L1 Tacho 1 N 2 1 L1 2 1 1 2 1 2 2 PE 1 PE 2 1 2 2 1 1 2 0 10V 1 4 2 1 3 2 GND 10V 1 PE 2 PE 1 N 2 L1 N 1 L1 2 Tacho SP23 b SP23 b 9 10 8 6 7 5 K1 A1 A2 10V 1 5 2 L1 1 1 2...

Page 19: ...PE Q2 1 2 3 4 5 6 K2 1 2 3 4 5 6 1 2 3 4 5 6 F2 L1 COM 1 2 2 L3 1 L3 2 NC 1 1 2 0 10V 1 3 2 L1 1 L1 2 SP27 b PE 1 PE 2 L2 1 L2 2 GND 1 4 2 1 2 3 4 5 6 K2 F5 1 2 Stouch 1 24VDC AC 2 24VAC DC 3 GND 4 R...

Page 20: ...ng Installation works can only be performed by trained and qualified personnel The device should be mounted firmly and rigidly so it s safe use would be ensured The device can be connected to pull the...

Page 21: ...g the impeller be careful not to balance set weight The fan must be cleaned at least twice a year depending on the contamination Regular cleaning of the fan prevents its imbalance Remove all accessori...

Page 22: ...ermal contacts or resistors have triggered Motor blocked Contact the manufacturer or its representative Fan can t reach nominal speed Regulating devices are not adjusted properly Check if control devi...

Page 23: ...2 damage caused by entering outside objects materials liquids 4 3 damage caused by natural disaster accident voltage change in the electricity network lightning etc 5 The company assumes no liability...

Page 24: ...n cleaning Once a year Heat exchanger cleaning Once a year Filter replacement Every 3 4 months NOTE The purchaser is required to fill in the Product maintenance table 2 At least 2 Look at the product...

Reviews: