Control Unit Display Codes
Display Code
Description
System Reaction
A01
Dry Running
If water level in the tank is low (less than half way up the
pump), allow the tank to refill and manually restart the unit
by pressing the power/enter button.
This error code indicates that the unit will enter into
protective shut down to protect the pump.
To restart the unit, press the power (enter) button.
If the problem persists, please contact Salamander
for technical advice.
Additional storage tanks can be connected to increase the
stored volume of water. Note: total stored water should not
exceed estimated usage for a 24 hour period.
A02
Current Overload
This code is displayed if the nominal pump current exceeds
4.8A. 4 automatic reset attempts will be performed by the
control unit before remaining off until manually reset. During
these attempts, the current will be displayed. To restart the
unit manually, press the power (enter) button. If the problem
persists, please contact Salamander for technical advice.
A04
Fast Cycling
(Hammering)
This code is displayed if the system loses pressure instantly
when the outlets are closed this will force the pump to
switch on and off in a fast cycle. The code is activated when
3 consecutive cycles occur quickly. Check the air pre-charge
pressure in the pressure vessel is 1.5 bar. To restart the
unit, press the power (enter) button If the problem persists,
please contact Salamander for technical advice.
A05
Pressure
Transmitter
Requires
Recalibration
Contact Salamander for technical advice if this code is
displayed.
Factory Reset (Control Unit)
Your unit is pre-set with its operating parameters during assembly and testing.
If your unit is failing to operate and if instructed to do so by the Salamander Tech Desk team,
please follow these instructions to reset your unit:
Press and hold
▲
+
▼
+
for 5 secs until the screen shows
“nc”
Press 10 times until the screen shows
“r50”
Press
▲
to change the value to
“r51”
Press - the screen will show “OFF”
Press “A” for 3 seconds to set the max pump operating current
- the number on screen will flash
Press
▲
or
▼
to display
4.8
Press - the screen will show “OFF”
Press
▲
for 3 seconds to set the cut in pressure - the number on screen
will flash
Press
▲
or
▼
to display
2.0
Press - the screen will show “OFF”
Press
▼
for 3 seconds to set the cut out pressure - the number on screen
will flash
Press
▲
or
▼
to display
2.8
Press the screen will show “OFF”
Press to restart the unit.
Your unit is now reset and ready to resume normal operation.
ENTER
START
STOP
bar
psi
A
A
PRESS.
In normal operation the control unit
displays pressure or current readings
directly from the pump in the tank unit.
An LED will be lit up to show whether
the pressure is being displayed (in
bar or psi) or whether current is being
displayed (in Amps).
12
13