Electrical specification
Electrical Service and Fusing
Warning: To avoid severe electrical shock, turn off
power before servicing controls.
Unit
must
be
installed
in
compliance
with
local
codes.
Route
power
wires
through
a
properly sized disconnect
switch.
Consult
the
wiring
diagrams
inside
the
cover of
the
electrical
box
to
complete
the
connection.
See
nameplate
for
proper
fuse
sizing,
minimum
circuit
ampacity
and
voltage requirements.
If
an
auxiliary
electrical
heater
is
used,
it
must
be installed
with
a
power
supply
separate
from
the
heat
pump.
Electrical Data
Power wire
Compressor
Fan
Motor
Model
Power
RLA
LRA
FLA
Total
current A
Min/Max
Voltage
Breaking
current
Wire
V
A
Number
diameter
L009
3.60
17.80
0.39 3.99
10 1.5mm2 3
L013
5.40
26.10
0.52 5.92
15 1.5mm2 3
L016
6.25
27.44
0.85 7.10
15 1.5mm2 3
L019
7.75
31.83
0.94 8.69
25 2.5mm2 3
220V/50/1
198/264
L024
9.30
36.80
1.11 10.41
25 2.5mm2 3
L030
11.90
61.00
1.40 13.30
32 2.5mm2 3
L036
13.10
68.20
2.07
15.17
32 4mm2 3
J043
6.30
44.00
2.00 8.30
25 2.5mm2 5
J052
7.20
50.00
3.82 11.02
25 2.5mm2 5
J062
8.20
57.00
4.06 12.26
32 2.5mm2 5
380V/50/3
342/418
J072
10.10
73.00
5.82
15.92
32 4mm2 5
7
Microprocessor control
1.Basic Features
3) High and low voltage protection
Mode selection:Cooling,Heating,Ventilation,Dehumidify,Auto.
High and low voltage protection shuts off
the unit the event the unit voltage is too
high or too low to protect the internal
components from damage.
Fan speed control:High,medium,low fan speed.
Power detection:170-250V ±5%
2.
Protection function
1)
Fan speed control
4) Low pressure switch bypass
Fan speed control is a standard feature with the
microprocessor control system. It Permits
Low pressure switch bypass ignores the
low Pressure input signal for 120 seconds
each time. The compressor starts to
eliminate nuisance trip and to al ow the
suction pressure to build at Startup.
motor operate with High/Medial/low speed to meet
different requirement
2) Safety lockout
5) Condensate overflow protection
Safety lockout prevents compressor operation if any
of the safety switches trip: high pressure switch, low
pressure switch or optional freezestat. The unit can be
reset from the wall thermostat or from the main unit
disconnect.
Condensate overflow protection stops
compressor operation if the drain pan
sensor detects moisture at the top of the
pan to prevent overflow due to clogged or
slowdraining condensate piping.