8000m Series
-
50
-
E012 Reserved
E013 Phase-lack of
output side
1: There is a broken wire
in
the output cable
2: There is a broken wire
in the motor winding.
3.: Output terminals are
loose
Check the wiring and
installation
E014 Inverter
overheat
1:Instantaneous over
current of inverter
2:Output short circuit
3: Cooling fans
of inverter stop or
damaged. Obstruction of
ventilation channel
4: Ambient temperature
is too high
5: The cables or
terminals are loose
6: Power circuit
abnormal
7: Control PCB board
abnormal
1: Refer to over current
solutions
2: Use the good wire
3: Replace cooling
fan and clear the
ventilation channel
4:Decrease the
ambient temperature
5:Inspect and tighten
the wire and terminals
6 and 7: Ask for
support
E015 External fault
External fault input
terminals take effect
Inspect external
equipment
E016 Communication
fault
1: Improper baud rate
setting
2: Receive wrong data
3: Communication is
interrupted for long time
1: Set proper baud rate
2: Push STOP/RESET
to reset and ask for
support
3: Check
communication devices
and cables
E017 Reserved