8000m Series
-
23
-
Function
Code
Function
Descriptions
Minimum
Unit
Factory
Setting
Modifica-
tion Type
F0.20
Default setting
0: No operation
1: Restore to factory
setting
2:Fault record clearing
0
●
F0.21
Parameter lock
setting
0: Unlock parameter
1: Lock parameter
0
○
F0.22
Acceleration/
deceleration
method
0: Linear method
1: Reserved
0
●
F0.23
Reserved
F0.24
Reserved
F0.25
Cooling fan
running method
(only for 4kW
and above
inverter)
0: Keep running when
power on
1: Automatic running
1
○
F1 Group: Start and Stop Parameters
F1.00
Start mode
0:Start directly
1:DC braking first and
then start
2:Speed tracing first and
then start
0
●
F1.01 Start frequency
0.00~10.00Hz
0.01Hz
1.50Hz
○
F1.02
Hold time of
start frequency
0.0~50.0s
0.1s
0.0s
○
F1.03
DC braking
current before
start
0.0~150.0%
0.1%
0.0%
○
F1.04
DC braking time
before start
0.0~50.0s
0.1s