PCD0
Technical data’s and circuit diagrams for the modular system
Page 46
ã
SAIA-Burgess Controls Ltd.
(HB_PCD0 26 766_E2.DOC)
26/766 E2
4.6.2
Data width, addressing and terminal assignment RIO 4 I 230 VAC
RIO 4 I 230 VAC
Bytes Inputs
Bytes Outputs
Data width
Byte 1
Byte 2
Not used
Bit
Terminal
0
X3.0/4.0
1
X3.1/4.1
2
X3.2/4.2
3
X3.3/4.3
4
5
6
7
Not
used
The Bit position can be changed with the
Byte-Swap instruction. See page 159.
1 Byte start addresses
2 Bit numbering
4.6.3
Specifications RIO 4 I 230 VAC
RIO 4 I 230 VAC
Order no.
PCD0.E500
Module ID
25d / 19h
Number of inputs
4
External power supply
None
Power consumption from external 24V power
supply
None
Power consumption from internal 5V power
supply
0.2 W
Inputs
Switching level
H level AC 159 to 253 V
L level AC 0 to 40 V
Input current
Min. H level (AC 159 V)
³
5 mA
Max. L level (AC 40 V)
³
2.3 mA
Isolation from internal bus
Yes, each channel separately via opto-electronic couplers
See also General specifications on page 162.