Appendix
PCD0
26/766 E2
(HB_PCD0 26 766_E2.DOC)
SAIA-Burgess Controls Ltd.
Page 181
15.2
Analog module data formats
The data formats are set using the parameterizing and diagnosis function of the respective bus
coupler (e.g. RIO BC or EC) or Master PLC (e.g. PCD2.M..). For a description of the parameterizing
and diagnosis functions refer to the respective operating manual.
The following data formats can be set:
Parameter
Data format
Suitable for
0
±
10 V in two’s complement (-2048 .... +2047)
RIO 4AI
±
10V
RIO 4AI/4AO
±
10V
1
±
10 V in mV (-10000 .... +10000)
RIO 4AI
±
10V
RIO 4AI/4AO
±
10V
2
0...20 mA in two’s complement (0...4095)
RIO 4AI 20mA
RIO 4AI/4AO 20M
RIO 4AI 4-20mA
(*1)
RIO 4AI/4AO 4-20mA
(*1)
3
0...20 mA in
µ
A (0...20000)
RIO 4AI 20mA
RIO 4AI/4AO 20mA
RIO 4AI 4-20mA
(*2)
RIO 4AI/4AO 4-20mA
(*2)
4
4...20 mA in S5 format
0 ... 20 mA module
RIO 4AI 20mA
RIO 4AI/4AO 20mA
5
0...10 V in mV (0 ... 10000)
RIO 4AI
0-
10V
RIO 4AI/4AO
0-
10V
7
4...20 mA in S7 format
8
4...20 mA in S5 format
4...20 mA modules
RIO 4AI 4-20mA
RIO 4AI/4AO 4-20mA
(*1)
= the range 0..4095 will be divided in the whole range of the 4-20mA module (0..22.81 mA)
(*2)
= the range 0..20000 will be divided in the whole range of the 4-20mA module (0..22.81 mA)
15.2.1
Voltage input/output data formats
±
10 V in two’s complement (-2048 ...
+2047)
Binary
Measured
value
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Dec.
Hex.
10,000 V
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
2047
07FF
5,000 V
0
0
0
0
0
1
0
0
0
0
0
0
0
0
0
0
1024
0400
0,000 V
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0000
-5,000 V
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
-1024
FC00
-10,000 V
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
-2048
F800
±10 V in mV (-10000...+10000)
Binary
Measured
value
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Dec.
Hex.
10,000 V
0
0
1
0
0
1
1
1
0
0
0
1
0
0
0
0
10000
2710
5,000 V
0
0
0
1
0
0
1
1
1
0
0
0
1
0
0
0
5000
1388
0,000 V
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
-5,000 V
1
1
1
0
1
1
0
0
0
1
1
1
1
0
0
0
-5000
EC78
-10,000 V
1
1
0
1
1
0
0
0
1
1
1
1
0
0
0
0
-10000 D8F0