19
Digital input
FWD
Forward operation /
Used for forward operation (when FWD-CM is on) or
Stop command
deceleration and stop (when FWD-CM is opened)
REV
Reverse operation /
Used for reverse operation (when REV-CM is on) or
Stop command
deceleration and stop (when REV-CM is opened)
X1
Digital input 1
The coast-to-stop command, external alarm, alarm reset, multi-
step frequency selection, and other functions (from an external
circuit) can be assigned to terminals X1 to X9. For details, see
"Setting the Terminal Functions E01 to E09" in Section 5.2
Function Explanation.
<Specifications of digital input circuit>
X2
Digital input 2
X3
Digital input 3
X4
Digital input 4
X5
Digital input 5
X6
Digital input 6
X7
Digital input 7
X8
Digital input 8
X9
Digital input 9
P24
Control Unit power Supply
+24VDC power supply for control input. Maximum output current 100mA
PLC
PLC signal power
Used to connect PLC power supply for output signals; rated nominal
voltage = 24 VDC (22 to 27 V DC range) at sink logic operation.
CM
Digital input common
Common terminal for digital input signals and P24
Analog output
FMA
Analog monitor
Outputs monitor signal using analog DC voltage 0 to +10V DC.
The signal indicates one of the following:
(11: common
- Output frequency (before slip compensation)
terminal)
- Load factor
- Output frequency (after slip compensation)
- Power consumption
- Output current
- PID feedback value
- Output voltage
- PG feedback value
- Output torque
- DC link circuit voltage
* Connectable impedance: min. 5k ohms
Pulse output
FMP
Frequency monitor
Outputs a monitor signal using the pulse waveform.
(CM: common
(pulse waveform output)
This signal has the same function as the FMA signal.
terminal)
Item
min.
typ.
max.
Operating voltage
ON
0V
–
2V
OFF
22V
24V
27V
Maximum load current
ON
–
3.2mA 4.5 mA
Leakage current
OFF
–
–
0.5 mA
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Summary of Contents for GP10
Page 5: ...4 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 34: ...33 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 35: ...34 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 36: ...35 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 37: ...36 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 39: ...38 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 50: ...49 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 52: ...51 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...