Important recommendations

 

Never allow an exposed flame or 

spark near the batteries, 

particularly while charging.

 

Never smoke while performing any 

operation on the battery.

 

For protection, wear rubber gloves, 

long sleeves, and appropriate 

splash goggles or face shield.

 

The electrolyte is harmful to skin 

and eyes. In the event of contact 

with skin or eyes, wash immediately 

with plenty of water. If eyes are 

affected, flush with water, and 

obtain immediate medical attention.

 

Remove all rings, watches and 

other items with metal parts before 

working on the battery.

 

Use insulated tools.

 

Avoid static electricity and take 

measures for protection against 

electric shocks.

 

Discharge any possible static 

electricity from clothing    

and/or tools by touching an  

earth-connected part "ground" 

before working on the battery.

1. Receiving the shipment

Unpack the cells immediately upon 
arrival. Do not overturn the package. 
Transport seals are located under the 
cover of the vent plug.
The cells are normally shipped filled, 
discharged and ready for assembly.

The cells must never be charged  

with the plastic transport seal in 

place as this can cause permanent 

damage.

2. Storage

Store the cells indoors in a dry, clean 
and cool location (0°C to +30°C / 
+32°F to +86°F). 

 

Do not store in unopened packing 

crates. The lid and the packing 

material on top of the cells must 

be removed.

 

Make sure that the transport seals 

remain in place during storage.

 Do not store in direct sunlight or 

exposed to excessive heat.

 Cells delivered discharged and filled 

may be stored for many years before 
it is installed.

 Cells delivered exceptionally 80% 

charged (for starting application) 
must not be stored 

more than 

3 months (including transport).

SPH Ni-Cd batteries

Installation and operating instructions

3. Electrolyte

The electrolyte to be used is: E4
When checking the electrolyte levels, a 
fluctuation in level between cells is not 
abnormal and is due to the different 
amounts of gas held in the separator  
of each cell. The level should be at least 
15 mm above the minimum mark (lower) 
and there is normally no need to adjust it.
When the cells are charged, the  
electrolyte level can be above the 
maximum level mark (upper).

4. Installation

4.1. Location

Install the battery in a dry and clean 
room. Avoid direct sunlight, strong 
daylight and heat.
The battery will give the best perfor-
mances and maximum service life when 
the ambient temperature is between 
+10°C to +30°C (+50°F to +86°F).

4.2. Ventilation

At normal float charge the gas  
evolution is very small but some 
ventilation is necessary. 

Note that special regulations for 

ventilation may be valid in your area 

depending on the application.

4.3. Mounting

Verify that cells are correctly  
interconnected with the appropriate 
polarity. The battery connection to load 
should be with nickel plated cable lugs.
Recommended torques for connecting  
nuts are:
• M 10 = 10 ± 2 N.m
• M 12 = 15 ± 2 N.m 
The connectors and terminal nuts  
should be corrosion-protected by 
coating with a film of neutral vaseline.

Remove the transport seals and  

close the vent plugs.

Install the IP2X protections according to 
the assembly instructions in Appendix A 
to have the battery compliant to IEC 
62485-2/EN 50272-2 standards for IP2 
level protection against electrical shocks.

5. Commissioning 

 

Verify that the transport seals are 

removed, the vents are closed and 

the ventilation is adequate during  

this operation.

A good commissioning is important. 
Charge at constant current is 
preferable. If the current is limit lower 
than indicated in the table A, charge 
for a proportionally longer time.

  

For filled and discharged cells 

stored up to 1 year,

 

a commissioning charge is normally 
not required and the cells are ready 
for immediate use. 
A commissioning charge as described 
in the following section is only 
recommended if full performances 
are necessary immediately.

 For cells stored more than 1 year

or for charged cells stored more 

than 3 months,

 a commissioning 

charge is necessary:

• Constant current charge:  

charge for 8 h at 0.2 C

A.  

 

When the charger maximum voltage 
setting is too low to supply constant 
current charging, divide the battery 
into two parts to be charged 
individually.

• Constant voltage charge:  

1.50 V/cell minimum for 24 h with 
current limited to 0.2 C

A, or for 48 h 

with current limited to 0.1 C

A.

Please note:

 if cells have been stored 

in charged conditions for more than 

3 months (including transport), or if 

cells have been stored for a few years 

or show difficulties in recovering 

performance, constant current 

charging becomes necessary and the 

following values are recommended:
a)  15 h charge at 0.2 C

A

b) Discharge at 0.2 C

A down to 

1.0 V/cell

c)  8 h charge at 0.2 C

A

d)  The battery is ready for use.

For capacity test purposes, the battery 

has to be charged in accordance with 

IEC 60623 section 4.

 

6. Charging in service

At continuous parallel operation, the  
battery is on continuous charge and 
has only occasional discharges.
Recommended charging voltage  
(+20°C to +25°C / +68°F to +77°F):

 

for dual charge level:

• Float level: 1.40 ± 0.01 V/cell
• High level: 1.45 ± 0.01 V/cell

March 2013