Saft SMRX-F3 Manual Download Page 2

 

SMRX160 F3

 

160 

32 

668

 SMRX180 F3

 

180 

36 

668

 SMRX200 F3

 

200 

40 

792

 SMRX230 F3

 

230 

46 

792

 SMRX260 F3

 

260 

52 

1041

 SMRX290 F3

 

290 

58 

1040

 SMRX320 F3

 

320 

64 

1206

 SMRX360 F3

 

360 

72 

1187

  

Capacity 

Charge  

Electrolyte  

  

C

5

Ah 

current 

reserve

 Cell type 

 

0.2 C

5

  

(Ah) 

(A) 

(cm

3

)

 Two level charge:

• High level: 1.43 - 1.50 V/cell  

at + 20°C (+ 68°F)

• Float level: 1.38 - 1.40 V/cell  

at + 20°C (+ 68°F)

For use at temperature o10°C 
to +30°C (+50°F to +86°F), the charge 
voltage correcting factor is:
• – 2 mV/°C/cell (– 1.1 mV/°F/cell)  

if charged voltage <1.45 V/cell at 
+ 20°C (+ 68°F)

• – 3 mV/°C/cell (– 1.7 mV/°F/cell)  

if charged voltage between 1.45  
and 1.55 V/cell at + 20°C (+ 68°F)

For higher charging voltages,  

consult Saft.

To minimise the water usage,  

Saft recommends the use of low 

charging voltages.

6. Topping-up

No electrolyte level measurement is 
required if a Saft Celltopper Plus is 
used which allows the correct level to 
be obtained by a simple nozzle setting 
when fitted with the correct spacer 
tube.

 Refer to Table B

 for cell type 

and corresponding spacer tube type. 
If a filling pistol is not available, a clean 
plastic filling bottle can be used for 
topping-up. Do not fill above the 
maximum (upper line) level. All topping-
up equipment shall be dedicated to 
Ni-Cd batteries.

7. Periodic maintenance

Periodic maintenance should be 
carried out every two years or as 
required. 

 

Keep the battery clean using only 
water. Do not use a wire brush or 
solvents of any kind. Vent plugs can 
be rinsed in clean water when dirty. 

 

Check the electrolyte level. Never 
let the level fall below the minimum 
(lower line) level. Use only distilled  
or deionized water for topping-up.

 

Frequency of topping-up must be 
determined for each battery.  
It depends on charging voltage, 
temperature and actual utilization  
of the battery. 

Refer to Section 6 

concerning topping-up

 

Check torque of all upper nuts 
(if supplied).

 

Apply a thin layer of neutral Vaseline 
or anti-corrosion coating agreed by 
Saft to all connectors and  terminal 
nuts (if applicable). 

 

Check charger settings. It is very 
important that the recommended 
charging voltage remains unchanged. 
High water consumption of the 
battery is usually caused by improper 
voltage setting of the charger

SMRX-F3 Ni-Cd batteries

Table A: 

Cell Data

 Cell type  

Spacer tube type

 

SMRX160 F3 

B

 SMRX180 F3 

B

 SMRX200 F3 

B

 SMRX230 F3 

B

 SMRX260 F3 

B

 SMRX290 F3 

B

 SMRX320 F3 

A

 SMRX360 F3 

A

Table B: 

Topping-up equipment (Celltopper Plus)*

* Refer to separate instructions for further information on Celltopper Plus. 

8. Changing electrolyte

Due to the sintered electrode / plastic 
bonded technology, it is not necessary 
to change the electrolyte during the 
life-time of the cell(s).

9. Battery service and recycling

Contact your Saft representative 
concerning battery testing.  
Saft America Inc. is licensed to receive 
and recycle spent batteries.  
To protect the environment all used 
batteries must be recycled.

Saft

Industrial Battery Group

 

Railway Sales
109 Beaver Court, Suite 200
Cockeysville, MD 21030 (USA)
Tel:  410-771-3200
Fax: 410-329-9802
711 Industrial Blvd
Valdosta, GA 31601 (USA)
Tel:  229-247-2331
Fax: 229-245-2890

www.saftbatteries.com

Doc 21819-2-0312 

Data in this document is subject to change without 

notice and becomes contractual only after written 

confirmation.
Société par Actions Simplifiée  

au capital de 31 944 000 

RCS Bobigny B 383 703 873

Le Révérend Imprimeur - Printed in France

Reviews: